PARAMETERS
4.2.7 DC injection brake (Pr. 10 to Pr. 12)
Pr. 10 "DC injection brake operation frequency"
Pr. 11 "DC injection brake operation time"
Pr. 12 "DC injection brake voltage"
By setting the DC injection brake voltage (torque), operation time and operation starting
frequency, the stopping accuracy of positioning operation, etc. or the timing of operating
the DC injection brake to stop the motor can be adjusted according to the load.
<Setting>
Use Pr. 10 to set the frequency at which the DC injection brake operation is started.
Use Pr. 11 to set the period during when the brake is operated.
Use Pr. 12 to set the percentage of the power supply voltage.
Parameter
Number
Factory
Setting
Setting
Range
10 3Hz 0 to 120Hz
11 0.5s 0 to 10 s
12 2% 0 to 30%
CAUTION
Install a mechanical brake. No holding torque is provided.
Operation
frequenc
y
DC injection
brake voltage
Output frequency (Hz)
Time
Time
Pr.12
Operation time
Pr.11
Pr.10
Operation
voltage