PARAMETERS
<Setting of stall prevention operation level>
In Pr. 22, set the stall prevention operation level. Normally set it to 150% (factory
setting). Set "0" in Pr. 22 to disable the stall prevention operation.
To reduce the stall prevention operation level in the high-frequency range, set the
reduction starting frequency in Pr. 66 and the reduction ratio compensation factor in
Pr. 23.
Formula for stall prevention operation level
Stall prevention operation level (%) = A + B
× [] × []
where, A = , B =
By setting "9999" (factory setting) in Pr. 23, the stall prevention operation level is
constant at the Pr. 22 setting up to 400Hz.
<Setting of stall prevention operation selection>
Refer to the following table and set the parameter.
Pr. 156
Setting
High-
Response
Current
Limit
: Activated
: Not
activated
Stall Prevention
Operation
Selection
: Activated
: Not activated
OL Signal
Output
:
Operation
continued
:
Operation
not
continued
(Note 1)
Pr. 156
Setting
High-
Response
Current
Limit
: Activated
: Not
activated
Stall Prevention
Operation
Selection
: Activated
: Not activated
OL Signal
Output
:
Operation
continued
:
Operation
not
continued
(Note 1)
Acceleration
Constant
speed
Deceleration
Acceleration
Constant
speed
Deceleration
0

16

1
 17 
2

18

3 

19 

4
  20 
5

21
6


22

7 
 23 
8

24


9

25


10
26 
11 
27 

12


28


13
 29 
14

30

15 
31 
100
Driving

Regenerative

Pr. 22-A
Pr. 22-B
Pr. 23-100
100
Pr. 66 (Hz) × Pr. 22 (%)
output frequency (Hz)
Pr. 66 (Hz) × Pr. 22 (%)
400Hz