Pr. 71 "applied motor"
Pr. 83 "rated motor voltage"
Pr. 84 "rated motor frequency"
Pr. 89 "speed control gain"
Pr. 90 to Pr. 94 (motor constants)
Pr. 95 "online auto tuning selection"
Pr. 96 "auto tuning setting/status"
Pr. 180 to Pr. 186
(input terminal function selection)
Related parameters
z
zz
z Motor capacity/number of motor poles/speed control gain (Pr. 80, Pr. 81, Pr. 89)
Pr. 80 "motor capacity"
Pr. 81 "number of motor poles"
Pr. 89 "speed control gain"
You can set the advanced magnetic flux vector control.
z Advanced magnetic flux vector control
Provides large starting torque and sufficient low-speed torque.
Effective for great load fluctuation.
Parameter
Number
Factory
Setting
Setting Range Remarks
80 9999 0.4K to 55kW, 9999 9999: V/F control
81 9999 2, 4, 6, 12, 14, 16, 9999 9999: V/F control
89 100% 0 to 200.0%
If any of the following conditions is not satisfied, faults such as torque shortage and speed fluctuation may
occur. In this case, select V/F control.
<Operating conditions>
·
The motor capacity is equal to or one rank lower than the inverter CT rating as the following table.
Inverter CT rating One rank lower capacity than inverter
0.75kW 0.4kW
2.2kW 1.5kW
3.7kW 2.2kW
7.5kW 5.5kW
15 kW 11 kW
22 kW 18.5 kW
37 kW 30 kW
55 kW 45 kW
·
Offline auto tuning must be performed.
·
The number of motor poles is any of 2, 4, and 6. (4 poles only for the constant-torque motor)
·
Single-motor operation (one motor for one inverter) is performed.
·
The wiring length between the inverter and motor is within 30m (98.42 feet). (If the length is over 30m
(98.42 feet), perform offline auto tuning with the cables wired.)