PARAMETERS
102
Parameter details
Parameter
Number
Setting Description
9 0 to 500A Set the rated motor current (A).
0
Electronic overcurrent protection thermal characteristics suitable for general-purpose
motor
1
Electronic overcurrent protection thermal characteristics suitable for constant-torque
motor
2
Electronic overcurrent protection thermal characteristics suitable for general-purpose
motor
5-point flexible V/F characteristics
3 Standard motor
13 Constant-torque motor
Select "offline auto tuning setting"
4 Standard motor
14 Constant-torque motor
Auto tuning read or change setting
enabled
5 Standard motor
15 Constant-torque motor
Star connection
6 Standard motor
16 Constant-torque motor
Delta connection
Direct input of
motor constants
enabled
7 Standard motor
17 Constant-torque motor
Star connection
8 Standard motor
71 (Note 1)
18 Constant-torque motor
Delta connection
Direct input of
motor constants
and offline auto
tuning
83 0 to 1000V Set the rated motor voltage (V).
84 50 to 120Hz Set the rated motor frequency (Hz).
90 0 to , 9999
91 0 to , 9999
92 0 to , 9999
93 0 to , 9999
9999
94
0 to 100%
Tuning data
(Values measured by offline auto tuning are set automatically.)
0 Offline auto tuning is not performed.
1 Offline auto tuning is performed without motor running.96 (Note 2)
101 Offline auto tuning is performed with motor running.
Note: 1. The electronic overcurrent protection characteristics are also selected simultaneously.
2. Select "101" to increase tuning accuracy.
(
2
)
Tuning execution
·
For PU operation, press the [FWD] or [REV] key.
·
For external operation, switch on the run command.
Note: 1. When "101" is set in Pr. 96, guard against hazards because the motor rotates.
2. To force tuning to end
·
Switch on the MRS or RES signal or press the [STOP] key to end.
·
Switch off the tuning start command or make a forced stop.
3. During offline auto tuning, the following I/O signals are only valid:
·
Input signals
STOP, OH, MRS, RT, CS, RES, STF, STR
·
Output signals
RUN, OL, IPF, FM, AM, A, B, C
4. Special caution should be exercised when a sequence has been designed to open the
mechanical brake with the RUN signal.
5. When performing offline auto tuning, switch on the main circuit power (R, S, T) of the inverter
and then enter the run command.