Monitoring the offline tuning status
When the parameter unit (FR-PU04) is used, the Pr. 96 value is displayed during tuning on the main
monitor as shown below. When the operation panel (FR-DU04) is used, only the same numerical value as
on the PU is displayed:
·
Parameter unit (FR-PU04) main monitor
(For inverter trip)
1. Setting
2. Tuning in
progress
3. Completion 4. Error-activated end
STOP PU
1
FWD PU
2
STF
TUNE
STOP PU
3
STF
TUNE
COMPLETION
Display
STOP PU
101
FWD PU
102
STF
TUNE
STOP PU
103
STF
TUNE
COMPLETION
STOP PU
9
STF
TUNE
ERROR
·
Operation panel (FR-DU04) display
(For inverter trip)
1. Setting
2. Tuning in
progress
3. Completion 4. Error-activated end
12 3
Displayed
value
101 102 103
9
·
Reference: Offline auto tuning time (factory setting)
Offline Auto Tuning Setting Time
1: No-rotation mode Approximately 25 seconds
2: Rotation mode
Approximately 40 seconds
(Offline auto tuning time varies with acceleration and deceleration time settings as
indicated below:
Offline auto tuning time = acceleration time + deceleration time + approximately 30
seconds)
(4)
Ending the offline auto tuning
1) Confirm the Pr. 96 value.
·
Normal end: "3" or "103" is displayed.
·
Error-activated end: "9", "91", "92" or "93" is displayed.
·
Forced end ... "8" is displayed.
2) When tuning ended normally.
For PU operation, press the [STOP] key. For external operation, switch off the start signal (STF or STR).
This operation resets the offline auto tuning and the PU's monitor display returns to the ordinary indication.
(Without this operation, next operation cannot be done.)
3) When tuning was ended due to an error.
Offline auto tuning did not end normally. (Motor constants have not been set.) Reset the inverter and start
tuning all over again.
4) Error display definitions.
Error Display Error Cause Remedy
9 Inverter trip Re-set.
91
Current limit (stall prevention) function was
activated.
Increase acceleration/deceleration time.
Set "1" in Pr. 156.
92
Inverter output voltage reached 75% of rated
value.
Check for fluctuation of power supply voltage.
93 Calculation error Check the motor wiring and re-set.
No connection with motor will result in 93 error.
4