PARAMETERS
106
Pr. 71 "applied motor"
Pr. 80 "motor capacity"
Pr. 81 "number of motor poles"
Pr. 83 "rated motor voltage"
Pr. 84 "rated motor frequency"
Pr. 89 "speed control gain"
Pr. 90 to Pr. 94 (motor constants)
Pr. 96 "auto tuning setting/status"
Related parameters
z To enter the Pr. 92 and Pr. 93 motor constants in [mH]
<Operating procedure>
1. Set "801" in Pr. 77. Only when the Pr. 80 and Pr. 81 settings are other than "9999", the parameter
values of the motor constants (Pr. 90 to Pr. 94) can be displayed. Though the parameter (Pr. 82 to
Pr. 99) values of other than the motor constants (Pr. 90 to Pr. 94) can also be displayed, they are
parameters for manufacturer setting and should be handled carefully without misuse.
2. Set any of the following values in Pr. 71:
·
Standard motor...................................................................................... Pr. 71 = "0"
·
Constant-torque motor........................................................................... Pr. 71 = "1"
3. In the parameter setting mode, read the following parameters and set desired values:
Parameter
Number
Name Setting Range
Setting
Increments
Factory
Setting
90 Motor constant R1 0 to 50, 9999 0.001 9999
91 Motor constant R2 0 to 50, 9999 0.001 9999
92 Motor constant L1 0 to 1000mH, 9999 0.1mH 9999
93 Motor constant L2 0 to 1000mH, 9999 0.1mH 9999
94 Motor constant X 0 to 100%, 9999 0.1% 9999
4. Refer to the following table and set Pr. 84:
Parameter
Number
Name Setting Range
Setting
Increments
Factory
Setting
84 Rated motor frequency 50 to 120Hz 0.01Hz 60Hz
5. Return the Pr. 77 setting to the original value.
Note: 1. Pr.90 to Pr. 94 values may only be read when the Pr. 80 and Pr. 81 settings are other than
"9999" (advanced magnetic flux vector control selected).
2. Set "9999" in Pr. 90 to Pr. 94 to use the standard motor constants (including those for the
constant-torque motor).
Pr. 89
Î
ÎÎ
Î
Refer to Pr. 80.
z
zz
z Online auto tuning selection (Pr. 95)
Pr. 95 "online auto tuning selection"
By online auto tuning, the motor conditions are tuned rapidly at the start. This enables precise operation
unaffected by motor temperatures and steady high-torque operation down to super-low speed. After setting
the Pr. 80 and Pr. 81 values, select online auto tuning with Pr. 95.
z Online auto tuning
Use this function when steady high-torque operation is required for low-speed operation under advanced
magnetic flux vector control.
·
Before starting the online auto tuning, perform the offline auto tuning. Data must be calculated.