Instruction manual

Table Of Contents
PARAMETERS
140
Setting
Positive
logic
Negative
logic
Signal
Name
Function Operation
Related
parameter
17  MC1
Commercial power supply-
inverter switch-over MC1
18  MC2
Commercial power supply-
inverter switch-over MC2
19  MC3
Commercial power supply-
inverter switch-over MC3
Refer to Pr. 135 to Pr.139 (commercial power
supply-inverter switch-over).
Pr. 135 to
Pr. 139
20 120 BOF Brake opening request
Refer to Pr. 278 to Pr. 285 (brake sequence
functions).
Pr. 278 to
Pr. 285
25 125 FAN Fan fault output Output when a fan fault occurs. Pr. 244
26 126 FIN Fin overheat pre-alarm
Output when the heat sink temperature reaches
about 85% of the fin overheat protection
temperature.

27 127 ORA In-position
28 128 ORM Orientation error
When orientation is valid (only when FR-A5AP
option is loaded)
29 129 Y29 Overspeed detection
30 130 Y30 Forward running output
31 131 Y31 Reverse running output
For PLG feedback control, vector control
(only when the FR-A5AP option is loaded)
32 132 Y32 Regeneration status output
33 133 RY2 Operation ready 2
For vector control
(only when the FR-A5AP option is loaded)

98 198 LF Minor fault output Output when a minor fault occurs. 
99 199 ABC Alarm output
Output when the inverter's protective function is
activated to stop the output (major fault).

9999  No function  
0 to 99: Positive logic
100 to 199: Negative logic
Note: 1. Under PLG feedback control (when the FR-A5AP option is loaded), the operations of the up-to-
frequency SU and frequency detection FU, FU2, FU3 are as follows:
SU, FU: The actual speed (frequency) provided by the PLG feedback signal is output at or above
the frequency specified for detection.
FU, FU3: The inverter output frequency is output at or above the frequency specified for
detection.
2. When the frequency setting is varied with the analog signal or the [UP/DOWN] key of the
operation panel, note that the output of the SU (up-to-frequency) signal may alternate between
ON and OFF due to that varying speed and the timing of the varying speed dependent on the
acceleration/deceleration time setting.
(Such alternation will not take place when the acceleration/deceleration time setting is "0
seconds".)
3. This signal is output when "5" is set in Pr. 79 "operation mode selection" and the external
operation mode is selected (the inverter goes into the programmed mode).
4. The same function may be set to more than one terminal.
5. When the function is activated, the terminal conducts with the settings of 0 to 99 and does not
conduct with the settings of 100 to 199.
6. Pr. 190 to Pr. 195 do not function if the values set are other than the above.
7. When Pr. 76 = 1 or 3, the output signals of the SU, IPF, OL and FU output terminals conform to
Pr. 76. When an inverter alarm occurs, the signal outputs are switched over to alarm code
outputs.
8. The output assignment of the RUN terminal and alarm output relay conforms to the above setting
independently of Pr. 76.