z Programmed operation function (Pr. 200 to Pr. 231)
Pr. 200 "program minute/second selection"
Pr. 201 to Pr. 210 "program setting 1 to 10"
Pr. 211 to Pr. 220 "program setting 11 to 20"
Pr. 221 to Pr. 230 "program setting 21 to 30"
Pr. 231 "time-of-day setting"
z In programmed operation, automatic operation is performed under the control of the internal timer in
accordance with the preset time of day, running frequency and rotation direction.
z This function is made valid when the following parameter is set to the following value:
·
Pr. 79 = "5" (programmed operation)
z You can select the time unit for programmed operation between "minute/second" and "hour/minute".
z The start time of day, rotation direction and running frequency are defined as one point and every 10 points
are grouped into three:
·
Group 1: Pr. 201 to Pr. 210
·
Group 2: Pr. 211 to Pr. 220
·
Group 3: Pr. 221 to Pr. 230
z Use Pr. 231 to set the time of day when programmed operation is started.
Parameter
Number
Factory
Setting
Setting Range Remarks
200 0 0 to 3
0, 2 [minute/second]
1, 3 [hour/minute]
201 to 210 0,9999,0
0 to 2
0 to 400, 9999
0 to 99.59
0 to 2: Rotation direction
0 to 400, 9999: Frequency
0 to 99.59: Time
211 to 220 0,9999,0
0 to 2
0 to 400, 9999
0 to 99.59
0 to 2: Rotation direction
0 to 400, 9999: Frequency
0 to 99.59: Time
221 to 230 0,9999,0
0 to 2: Rotation direction
0 to 400, 9999: Frequency
0 to 99.59: Time
0 to 2: Rotation direction
0 to 400, 9999: Frequency
0 to 99.59: Time
231 0 0 to 99.59
<Wiring example>
·
For sink logic
STF
RH
RM
RL
STR
SD
FU
OL
PF
SU
SE
I
1
2
3
U,V,W
Output signal common
Programmed
operation start
Group selection
Timer reset
Input signal common
Inverter
Motor
Terminal function Pr. 79 = 5
Terminal function Pr. 76 = 3
Group run signals
(Open collector)
Time-out signal
R,S,T
Pr. 76 "alarm code output selection"
Pr. 79 "operation mode selection"
Related parameters