- CHAPTER 5 PROTECTIVE FUNCTIONS
- 5.1 Errors (Alarms)
- 5.2 Troubleshooting
- 5.2.1 Motor remains stopped.
- 5.2.2 Motor rotates in opposite direction.
- 5.2.3 Speed greatly differs from the setting.
- 5.2.4 Acceleration/deceleration is not smooth.
- 5.2.5 Motor current is large.
- 5.2.6 Speed does not increase.
- 5.2.7 Speed varies during operation.
- 5.2.8 Operation mode is not changed properly.
- 5.2.9 Operation panel (FR-DU04) display is not provided.
- 5.2.10 POWER lamp is not lit.
- 5.2.11Parameter write cannot be performed
- 5.3 Precautions for Maintenance and Inspection
- CHAPTER 6 SPECIFICATIONS
- CHAPTER 7 OPTIONS
- APPENDICES
- REVISIONS
PROTECTIVE FUNCTIONS
173
Operation Panel
Indication
E.OV1
FR-PU04 OV During Acc
Name Regenerative overvoltage shut-off during acceleration
Description
If regenerative energy causes the inverter's internal main circuit DC voltage to
reach or exceed the specified value, the protective circuit is activated to stop the
inverter output. It may also be activated by a surge voltage generated in the
power supply system.
Check point Check for too slow acceleration.
Corrective action Decrease the acceleration time.
Operation Panel
Indication
E.OV2
FR-PU04 Stedy Spd OV
Name Regenerative overvoltage shut-off during constant speed
Description
If regenerative energy causes the inverter's internal main circuit DC voltage to
reach or exceed the specified value, the protective circuit is activated to stop the
inverter output. It may also be activated by a surge voltage generated in the
power supply system.
Check point Check for sudden load change.
Corrective action • Keep load stable.
Operation Panel
Indication
E.OV3
FR-PU04 OV During Dec
Name Regenerative overvoltage shut-off during deceleration or stop
Description
If regenerative energy causes the inverter's internal main circuit DC voltage to
reach or exceed the specified value, the protective circuit is activated to stop the
inverter output. It may also be activated by a surge voltage generated in the
power supply system.
Check point Check for sudden speed reduction.
Corrective action
• Increase the deceleration time. (Set the deceleration time which meets load
GD
2
)
• Decrease the braking duty.
5