Instruction manual
Table Of Contents
- SAFETY INSTRUCTIONS
- CONTENTS
- CHAPTER 1 OUTLINE
- CHAPTER 2 INSTALLATION AND WIRING
- CHAPTER 3 OPERATION/CONTROL
- CHAPTER 4 PARAMETERS
- CHAPTER 5 PROTECTIVE FUNCTIONS
- 5.1 Errors (Alarms)
- 5.2 Troubleshooting
- 5.2.1 Motor remains stopped.
- 5.2.2 Motor rotates in opposite direction.
- 5.2.3 Speed greatly differs from the setting.
- 5.2.4 Acceleration/deceleration is not smooth.
- 5.2.5 Motor current is large.
- 5.2.6 Speed does not increase.
- 5.2.7 Speed varies during operation.
- 5.2.8 Operation mode is not changed properly.
- 5.2.9 Operation panel (FR-DU04) display is not provided.
- 5.2.10 POWER lamp is not lit.
- 5.2.11Parameter write cannot be performed
- 5.3 Precautions for Maintenance and Inspection
- CHAPTER 6 SPECIFICATIONS
- CHAPTER 7 OPTIONS
- APPENDICES
- REVISIONS
SPECIFICATIONS
195
Protective/alarm functions
Overcurrent shut-off (during acceleration, deceleration, constant speed), regenerative
overvoltage shut-off, undervoltage, instantaneous power failure, overload shut-off (electronic
overcurrent protection), brake transistor alarm (Note 2), ground fault current, output short
circuit, main circuit device overheat, stall prevention, overload alarm, brake resistor overheat
protection, fin overheat, fan fault, option fault, parameter error, PU disconnection
Ambient temperature
Constant torque: -10°C to +40°C (14°F to 104°F) (non-freezing)
(-10°C to +30°C with FR-A5CV attachment)
Variable torque: -10°C to +40°C (14°F to 104°F) (non-freezing)
(-10°C to +30°C with FR-A5CV attachment)
Ambient humidity 90%RH or less (non-condensing)
Storage temperature
(Note 3)
-20°C to +65°C (-4°F to +149°F)
Ambience Indoors. (No corrosive and flammable gases, oil mist, dust and dirt.)
Environment
Altitude, vibration
Maximum 1000m (3280.80 feet) above sea level for standard operation.
After that derate by 3% for every extra 500m up to 2500m (91%).
5.9 m/s
2
{0.6G} or less (conforming to JIS C0911)
Note: 1. Jog operation may also be performed from the operation panel or parameter unit.
2. Not provided for the M4500-025 to 100 which do not have a built-in brake circuit.
3. Temperature applicable for a short period in transit, etc.