INSTALLATION AND WIRING
25
(2)
Connection of the power factor improving DC reactor
Connect the power factor improving DC reactor
between terminals P1-P. In this case, the jumper
connected across terminals P1-P must be
removed. Otherwise, the reactor will not function.
<Connection method>
P1 P
Remove
t
he jumper.
Note: 1. The wiring distance should be within 5m.
2. The size of the cables used should be equal to or larger than that of the power supply cables
(R, S, T).