Instruction manual

Table Of Contents
PARAMETERS
49
Func-
tion
Parameter
Number
Name Setting Range
Minimum
Setting
Increments
Factory Setting
Refer
To
Page:
Customer
setting
52 DU/PU main display data selection
0 to 20, 22, 23, 24,
25, 100
1076
53 PU level display data selection
0 to 3, 5 to 14,
17, 18
1176
54 FM terminal function selection
1 to 3, 5 to 14,
17, 18, 21
1176
55 Frequency monitoring reference 0 to 400Hz 0.01Hz 60Hz 78
Display functions
56 Current monitoring reference 0 to 500A 0.01A
Rated output
current
78
57 Restart coasting time 0, 0.1 to 5 s, 9999 0.1 s 9999 79
Automatic
restart
functions
58 Restart cushion time 0 to 60 s 0.1 s 1.0 s 79
Additional
function
59 Remote setting function selection 0, 1, 2 1 0 81
60 Intelligent mode selection 0 to 8 1 0 82
61 Reference I for intelligent mode 0 to 500A, 9999 0.01A 9999 83
62 Ref. I for intelligent mode accel. 0 to 200%, 9999 0.1% 9999 84
63 Ref. I for intelligent mode decel. 0 to 200%, 9999 0.1% 9999 84
64 Starting frequency for elevator mode 0 to 10Hz, 9999 0.01Hz 9999 84
65 Retry selection 0 to 5 1 0 85
66
Stall prevention operation level
reduction starting frequency
0 to 400Hz 0.01Hz 60Hz 67
67 Number of retries at alarm occurrence 0 to 10,101 to 110 1 0 85
68 Retry waiting time 0 to 10 s 0.1 s 1 s 85
69 Retry count display erasure 0

085
70 Special regenerative brake duty
0 to 15%/0 to 30%
(Note 9)
0.1% 0% 70
71 Applied motor 0 to 8, 13 to 18 1 0 87
72 PWM frequency selection 0 to 15 1 2 88
73 0-5V/0-10V selection 0 to 5, 10 to 15 1 1 89
74 Filter time constant 0 to 8 1 1 90
75
Reset selection/disconnected PU
detection/PU stop selection
0 to 3, 14 to 17 1 14 90
76 Alarm code output selection 0, 1, 2, 3 1 0 92
77 Parameter write disable selection 0, 1, 2 1 0 93
78 Reverse rotation prevention selection 0, 1, 1 0 94
Operation selection functions
79 Operation mode selection 0 to 8 1 0 95
80 Motor capacity 0.4 to 55kW, 9999 0.01kW 9999 98
81 Number of motor poles
2, 4, 6, 12, 14,
16, 9999
1 9999 98
82 Motor exciting current (Note 3) 0 to , 9999 1 9999 100
83 Rated motor voltage 0 to 1000V 0.1V 575 100
84 Rated motor frequency 50 to 120Hz 0.01Hz 60Hz 100
89 Speed control gain 0 to 200.0% 0.1% 100% 98
90 Motor constant (R1) (Note 3) 0 to, 9999 9999 100
91 Motor constant (R2) (Note 3) 0 to, 9999 9999 100
92 Motor constant (L1) (Note 3) 0 to, 9999 9999 100
93 Motor constant (L2) (Note 3) 0 to, 9999 9999 100
94 Motor constant (X) 0 to, 9999 9999 100
95 Online auto tuning selection 0, 1 1 0 106
Advanced magnetic flux vectorcontrol
96 Auto tuning setting/status 0, 1, 101 1 0 100
100 V/F1 (first frequency) (Note 1) 0 to 400Hz, 9999 0.01Hz 9999 108
101 V/F1 (first frequency voltage) (Note 1) 0 to 1000V 0.1V 0 108
102 V/F2 (second frequency) (Note 1) 0 to 400Hz, 9999 0.01Hz 9999 108
103 V/F2 (second frequency voltage) (Note 1) 0 to 1000V 0.1V 0 108
104 V/F3 (third frequency) (Note 1) 0 to 400Hz, 9999 0.01Hz 9999 108
105 V/F3 (third frequency voltage) (Note 1) 0 to 1000V 0.1V 0 108
5-point flexible V/F
characteristics
106 V/F4 (fourth frequency) (Note 1) 0 to 400Hz, 9999 0.01Hz 9999 108
Parameter List