PARAMETERS
50
Func-
tion
Parameter
Number
Name Setting Range
Minimum
Setting
Increments
Factory Setting
Refer
To
Page:
Customer
setting
107
V/F4 (fourth frequency voltage)
(Note 1)
0 to 1000V 0.1V 0 108
108 V/F5 (fifth frequency) (Note 1) 0 to 400Hz, 9999 0.01Hz 9999 108
5-point flexible V/F
characteristics
109
V/F5 (fifth frequency voltage)
(Note 1)
0 to 1000V 0.1V 0 108
110 Third acceleration/deceleration time
0 to 3600 s/
0 to 360 s, 9999
0.1 s/0.01 s 9999 60
111 Third deceleration time
0 to 3600 s
/0 to 360 s, 9999
0.1 s/0.01 s 9999 60
112 Third torque boost (Note 1) 0 to 30.0%, 9999 0.1% 9999 56
113 Third V/F (base frequency) (Note 1) 0 to 400Hz, 9999 0.01Hz 9999 58
114
Third stall prevention operation
current
0 to 200% 0.1% 150% 74
115
Third stall prevention operation
frequency
0 to 400Hz 0.01Hz 0 74
Third functions
116 Third output frequency detection 0 to 400Hz, 9999 0.01Hz 9999 73
117 Station number 0 to 31 1 0 109
118 Communication speed 48, 96, 192 1 192 109
119 Stop bit length/data length
0, 1 (data length 8)
10, 11
(data length 7)
1 1 109
120 Parity check presence/absence 0, 1, 2 1 2 109
121 Number of communication retries 0 to 10, 9999 1 1 109
122 Communication check time interval
0, 0.1 to 999.8 s,
9999
0.1 s 0 109
123 Waiting time setting 0 to 150ms, 9999 1ms 9999 109
Communication functions
124 CR, LF presence/absence selection 0,1,2 1 1 109
128 PID action selection 10, 11, 20, 21

10 119
129 PID proportional band
0.1 to 1000%,
9999
0.1% 100% 119
130 PID integral time
0.1 to 3600 s,
9999
0.1 s 1 s 119
131 Upper limit 0 to 100%, 9999 0.1% 9999 119
132 Lower limit 0 to 100%, 9999 0.1% 9999 119
133 PID action set point for PU operation 0 to 100% 0.01% 0% 119
PID control
134 PID differential time
0.01 to 10.00 s,
9999
0.01 s 9999 119
135
Commercial power supply-inverter
switch-over sequence output terminal
selection
0, 1 1 0 126
136 MC switch-over interlock time 0 to 100.0 s 0.1 s 1.0 s 126
137 Start waiting time 0 to 100.0 s 0.1 s 0.5 s 126
138
Commercial power supply-inverter
switch-over selection at alarm
occurrence
0, 1 1 0 126
Commercial power supply-
inverter switch-over
139
Automatic inverter-commercial power
supply switch-over frequency
0 to 60.00Hz,
9999
0.01Hz 9999 126
140
Backlash acceleration stopping
frequency (Note 6)
0 to 400Hz 0.01Hz 1.00Hz 69
141
Backlash acceleration stopping time
(Note 6)
0 to 360 s 0.1 s 0.5 s 69
142
Backlash deceleration stopping
frequency (Note 6)
0 to 400Hz 0.01Hz 1.00Hz 69
Backlash
143
Backlash deceleration stopping time
(Note 6)
0 to 360 s 0.1 s 0.5 s 69
Display
144 Speed setting switch-over
0, 2, 4, 6, 8, 10,
102, 104, 106,
108, 110
1472