PARAMETERS
64
Pr. 0 "torque boost"
Pr. 80 "motor capacity"
Pr. 81 "number of motor poles"
Pr. 180 to Pr. 186
(input terminal function selection)
Related parameters
z
zz
z Load pattern selection (Pr. 14)
Pr. 14 "load pattern selection"
You can select the optimum output characteristic (V/F characteristic) for the application and load
characteristics.
Parameter
Number
Factory
Setting
Setting Range
14 0 0 to 5
100%
Pr.14=0
Output frequency (Hz)
For constant-torque loads
(e.g. conveyor, cart)
Output voltage
Base frequenc
y
Output frequency (Hz)
For variable-torque loads
(Fan, pump)
100%
Output voltage
Base frequenc
y
Pr.14=1
Output frequency (Hz)
F
or lift
B
oost for forward rotation...Pr. 0 setting
B
oost for reverse rotation...0%
100%
Pr.0
Output voltage
Forward
rotation
Reverse
rotation
Base frequency
Pr.14=2
100%
Pr.0
Pr.14=3
Output frequency (Hz)
For lift
Boost for forward rotation...0%
Boost for reverse rotation...Pr. 0 setting
Output voltage
Reverse
rotation
Forward
rotation
Base frequency
Setting Output Characteristics Application
0 For constant-torque load Conveyor, cart, etc.
1 For variable-torque load Fan, pump
2 Boost for reverse rotation 0% Boost for forward rotation...Pr. 0 setting
3
For constant-
torque lift
Boost for forward rotation 0% Boost for reverse rotation...Pr. 0 setting
For lift load
ON...For constant-torque load (same as in setting = 0)
4 RT signal
OFF...For constant-torque lift, boost for reverse rotation 0% (same as in
setting = 2)
ON...For constant-torque load (same as in setting = 0)
5 RT signal
OFF...For constant-torque lift, boost for forward rotation 0% (same as in
setting = 3)
Load pattern selection
switching function using
RT signal
Note: 1. This parameter setting is ignored when Pr. 80 and Pr. 81 have been set to select the advanced
magnetic flux vector control mode.
2. When the RT signal is on, the other second functions such as second acceleration/deceleration
time and second torque boost are also selected.
3. When the setting is 4 or 5, X17 signal may be used instead of the RT signal. Use any of Pr. 180
to Pr. 186 to assign the terminal used to input the X17 signal.