The design of the device enables its safe mounting and proper fixation even if lifted accidentally. There are slots for safety screws
accessible after dismounting a front fibreglass cover, located in the top corners of the rear plate. There is an arrow that indicates
safety screw slots in the rear plate. The safety screw is fixed through a slot in the rear plate into a wall fastener. It prevents the
device from being pulled out and from falling out from a mounting bracket. At the same time, it secures a vertical position of the
device together with a device alignment with a wall.
6.4. Position assuring of the device
EN
Condensed water is drained from the device by the force of gravity. It is necessary to locate the device in a way that enables
sufficient condensed water gradient. The condensate must be delivered through a siphon into the sewer or into the outside
environmemt. It is strictly forbidden to deliver the condensate back into the swimming pool, as it may be bacterially contaminated.
There is a tube for condensed water delivery located at the bottom of the device, on the left side. This tube must be pluged into a
sewerage pipe with an internal diameter of minimum 16 mm.
6.5. Condensate drain
DRY 300i Silver and DRY 500i Silver with connections (front view)
Connecting the device onto the mains and protection securing must satisfy the requirements of relevant norms. Connection
requirements are the following: 220-240 V/50Hz, protection 10A (DRY 300i Silver) and 16A (DRY 500i Silver) with a mains-fuse that
has a current-carrying differential disconnecting capacity, not exceeding 30mA. There is a terminal for connection to the mains,
located on the left hand side of the device. The master switch of the device must be located outside the swimming pool area, it must
be bipolar and with L and N conductors´ disconnecting. The device for disconnecting the appliance from the mains must be inbuilt
to a steady point. There has to be a distance of min. 3 mm between the contacts (when switched off) for all the poles. Connection of
the device to the mains must be performed by a certified electrician.
6.6 Connecting the device to the mains
Preparation of electric power supply, condensate drain and console mounting
REAR PLATE
SAFETY SCREW SLOTS
CONDENSED WATER DELIVERY (AT THE BOTTOM OF THE DEVICE)
PIPE WITH AN INTERNAL DIAMETER OF MINIMUM 16 mm
POWER SUPPLY (AT THE BOTTOM OF THE DEVICE)
2
CYSY WIRE 3C x 1,5 mm
EN - WALL-MOUNTED SWIMMING POOL DEHUMIDIFIER - OWNER´S & INSTALLATION MANUAL