Owner`s manual

OM-263 001 Page 29
6-6. Setpoint Adjustment Table
Parameters Description Setting Range Factory Default Units Function
All All Combines differential pressure
P (ΔP) based cleaning with down-
time cleaning On/Off selectable from
keypad.
P6 Mode Select DTC All −− DTC Filters down-time cleaned
only, not based on filterΔP.
DFF DFF filter cleaning based on ΔP
with downtime cleaning not available.
P7 Display Units
0 = in. w.g.
1 = daPa
0 1 0 −− Selects units of measure for the
digital display.
P8 Downtime Start
Relay
30 99 30 Seconds Adjustable time lag between the
pressure dropping below the value
set in parameter P11 and the start of
the downtime cleaning.
P9 Downtime Pressure
Enable Relay
30 99 30 Seconds Adjustable time required to be above
the value set as the Low Set Point
(Lo) before the downtime feature is
enabled.
P10 Downtime Cleaning
Time
1 999 10 Minutes The amount of time the downtime
cleaning will continue once the time
set in P9 expires.
If the downtime cleaning se-
quence is in progress and the
pressure drop indicates a fan re-
start, the cleaning sequence will
end.
P11 Downtime Start
Pressure
0 9.6 (245) 0.3 (13) In. Water (daPa) The falling pressure that triggers the
downtime cleaning sequence.
If P11 is set as equal or greater
than the Lo value, the Lo value will
automatically increase 0.2 in.
above the P11 value.
P12 Pressure Sensor
Input Filtering
0 2 0 −− Sets the time used for ΔP value av-
eraging (0 = 250 ms, 1 = 2.5 sec, 2 =
10 sec).
P13 Reset to
Factory Defaults
0 1 0 −− 0 = No Reset
1 = Reset
P14 Zero Offset 0 1 0 −− 0 = No Operations
1 = Offset and Displayed Zero
P15 Software Version −− −− −− −−
P16 Password −− −− −− Factory password, no user-ad-
justable items in subsequent para-
meters.