MCP-E Series User's Manual
English TABLE OF CONTENTS MCP-E Series User's Manual 1. Introduction 2 2. Controls and Indicators 4 3. Installation 6 4. Operation 13 5. Troubleshooting 17 6. Replacing the Battery 20 7. Obtaining Service 24 8. Specifications 25 9. Configurable Parameters & Settings 26 10. Limited Product Warranty 28 11. Declaration of Conformity 29 © Copyright Para Systems, Inc.
INTRODUCTION English Thank you for purchasing a MINUTEMAN™ power protection product. It has been designed and manufactured to provide many years of trouble free service. IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS ! Please read the manual before installing your UPS. It provides the information that should be followed during installation and maintenance of the UPS and the batteries allowing you to correctly set up your system for the maximum safety and performance.
WARNING: Risk of electrical shock. Hazardous live parts inside this power supply are energized from the battery even when the AC input power is disconnected. To de-energize the outputs of the UPS: 1. If the UPS is on press the on/off button for 1 second 2. Disconnect the UPS from the AC power outlet 3. To deenergize the UPS completely, disconnect the battery. This uninterruptible power source contains potentially hazardous voltages. DO NOT attempt to disassemble the unit.
CONTROLS AND INDICATORS English FRONT PANEL (LCD Units) Primary Power Switch: Press and release the ON/OFF button to turn the unit ON or OFF. Normal Mode Icon: This icon will illuminate when the utility power is within safe operating range. Battery Mode Icon: This icon will illuminate when the Utility power is outside safe operating range and the unit is operating in the battery mode. Bypass Mode Icon: This icon will illuminate when the unit is in bypass mode and you do not have battery backup protection.
Unit Output Icon: When selected, this will display the selected item for the output from unit. Unit Amperage Icon: When selected, this will display the amps from either the input or output based on selection of input or output as described previously. Unit Voltage Icon: When selected, this will display the voltage from either the input or output based on selection of input or output as described previously.
INSTALLATION English INSTALLATION PLACEMENT Install the UPS in a temperature controlled environment that is free of conductive contaminants. Select a location which will provide good air circulation for the UPS at all times. Avoid locations near heating devices, water or excessive humidity, or where the UPS is exposed to direct sunlight. Route power cords so they cannot be walked on or damaged.
English 1 2 3 4 7 8 5 6 9 10 MCP 5000iE and MCP 7000iE 1. Fans: Internal Cooling Fans. 2. Maintenance Bypass Switch: In normal operation the switch must be in the UPS position. When doing routine maintenance the switch must be in the BPS position. 3. Output Circuit Breakers: Turn OFF/ON the output of the UPS. 4. Alarm Silencer: Silences the Alarm in the Battery Mode. 5. Configuration Switches: Must be set before turning the UPS ON (see page 8). 6.
INSTALLATION (Must be performed by Authorized Service Personnel ONLY) English Be sure to read the installation placement and all the cautions before installing the UPS. The MCP-E series UPS has external Battery Pack capability, please observe the following warning when connecting the Battery Pack(s). WARNING! DO NOT PLUG THE BATTERY PACK'S CONNECTOR INTO THE UPS's BATTERY CONNECTOR WHILE THE UPS IS TURNED ON.
NOTE: The MCP 5000iE and 7000iE's AC input must be connected to an AC circut breaker which will provide for an emergency power off. (Must be performed by Authorized English Service Personnel ONLY) Model MCP 5000iE MCP7000iE Input Circuit Breaker 40 Amp 50 Amp Input Wire Size/Temp 8 AWG/min75°C 6 AWG/min75°C Wire Conductor Three conductor, copper wire only Tightening torque for Torque 17.
Installation of the mounting tray and the stablizing feet. (Must be performed by Authorized Service Personnel ONLY) English The MCP 5000iE and the MCP 7000iE must be installed into a stationary position due to the hardwiring of the input and the output. 1. Move the UPS into the desired location. 2. Lay the mounting tray on the floor next to the UPS as shown below. 3. Roll the UPS onto the mounting tray. 4.
The Rackmount Configuration comes with mounting brackets for the standard 19" (46.5cm) rack. The mounting brackets to fit a 23" (59.2cm) standard rack are also available. The screws for mounting the UPS to the rack are not included (screw size varies with rack size). The kit includes, two mounting brackets and four retaining screws. Locate the mounting bracket screw holes on the side panels of the UPS, at the front of the UPS. Align the mounting bracket with the mounting bracket screw holes.
CONNECTING TO AN AC SOURCE English Plug the UPS into a two pole, three wire, grounded receptacle only. Do not use extension cords, adapter plugs, power strips or surge strips. The MCP 5000iE and MCP 7000iE must be hardwired (see page 8). COMPUTER INTERFACE CONNECTION (OPTIONAL) MINUTEMAN Power Management software and interface cables kits can be used with the MCP-E units. Use only MINUTEMAN or MINUTEMAN approved interface cables with these UPS’s.
English OPERATION TURNING THE UNIT ON/OFF The UPS is shipped with the unit disabled. Turn dip switch #1 to the ON position before attempting to turn on the unit. This will enable the unit. Set all of the dipswitches per the desired setting for your environment prior to turning on the unit. Turning ON/OFF the 700/1000VA To turn ON the 700/1000VA. Plug the input power cord into the AC wall outlet. Push and hold the ON/OFF button (on the front panel) for one beep, then release the button.
English MCP 2000 and MCP 3000. RS232 Port, Control Port pinouts and Confirguation Switches. Configuration Switches for the MCP 2000/3000/5000/7000. The "System Enable" switch must be enabled for the UPS to operate.
Place your unit in the desired location for use. Connect all equipment power cords to the receptacles on the rear of the UPS. Please insure you confirm total power requirements and do not overload the units. English Press and release the main power switch on the front of the unit to turn on the unit. Press and release again to turn off the unit. Some models have a circuit breaker on the rear panel that must be turned ON first and then press the front panel switch to turn the unit ON.
Communications port information for 2KVA, 3KVA, 5KVA and 7KVA units only: English These units contain two independent communications ports. Port one is for standard RS232 communications and labeled RS-232 Port. The second port is relay contact closure configured for standard AS 400 ports. This port is labeled Control Port. The pinout for the RS-232 port is depicted per the chart below. Note: when using the SNMP option card, this port will be disconnected.
English TROUBLESHOOTING Symptom WhatToDo PossibleCause E10 is displayed after Configuration dip switch is in turning on unit the off position Turn Dip Switch #1 to on position as defined on page 13 No AC utility power present When turned on, the unit operates in battery and unit Cold start function is enabled mode only Check utility input power and contact local service company if required to correct utility problem The unit switches from The fluctuation of the input utility Check the input utility
If your unit should have a problem, please call our Technical Support department to resolve any issues. Please call, 800-238-7272 or 972-446-7363 and ask for Technical Support. When you call with a problem, please be prepared to provide the following information to the technician.
Diagnostic Error Codes for 2KVA, 3KVA, 5KVA, 7KVA units Description E00 System ROM checksum error. E01 System RAM data read/write error. E02 System EEPROM data read/write error. E03 Communication fail between CPU & DSP E05 Temperature over 100oC. E07 Battery voltage is over specification (AC mode). E08 Input voltage fail (Outside of safe operating range & cold start disable). E10 Configure SW1 is set position “OFF”. E11 AC Mode input out of range during normal startup.
REPLACING THE BATTERY English REPLACING THE BATTERY (Must be performed by Authorized Service Personnel ONLY) The Tower Series UPS has a replacable battery(s), however the unit must be turned off, disconnected from utility and discharged prior to changing the batteries. The Rack Mount Series UPS has a hot swappable battery kit. Please read the following warning statements before attempting to service the battery(s).
A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed when working on batteries: 1. Remove watches, rings, or other metal objects. 2. Use hand tools with insulated handles. 3. Wear rubber gloves and boots. 4. Do not lay tools or other metal parts on top of batteries. 5. Disconnect charging source prior to connecting or disconnecting battery terminals. 6. Determine if the battery is inadvertently grounded.
Battery Replacement Procedure for Tower Model (Must be performed by Authorized Service Personnel ONLY) English PLEASE READ THE CAUTIONS BEFORE ATTEMPTING TO REPLACE THE BATTERIES These units are not hot-swappable. Hot-swappable batteries means that the batteries can be replaced without powering down the whole UPS system. 1. Turn off the equipment that is plugged into the output receptacles of the UPS. 2. Turn off the UPS using the primary power switch on the front. 3.
Battery Replacement Procedure for Rack Mount Models PLEASE READ THE CAUTIONS BEFORE ATTEMPTING TO REPLACE THE BATTERIES These units are hot-swappable. Hot-swappable batteries means that the batteries can be replaced without powering down the whole UPS system. NOTE: If there is a power interruption while replacing the hot-swappable batteries, with the UPS on, the load will not be backed up. 1. Utitlize steps 1-5 from page 22 if you do not want to hot-swap. Then proceed. 2.
OBTAINING SERVICE English IF THE UPS REQUIRES SERVICE 1.Use the TROUBLESHOOTING section to eliminate obvious causes. 2.Verify there are no circuit breakers tripped. A tripped circuit breaker is the most common problem. 3.Call your dealer for assistance. If you cannot reach your dealer, or if they cannot resolve the problem call or fax MINUTEMAN Technical Support at the following numbers; Voice phone (972) 446-7363 or 800-238-7272, FAX line (972) 446-9011 or visit our Web site at www.minutemanups.
NOTE: 230Vac Specs Shown In ( ) Topology Case Type Agency Approvals MCP 700 E MCP 1000 E MCP 2000 E Realized Power Output Limit Frequency Range Output (Non-Battery Operation) Output voltage Frequency Surge energy rating (one time, 10/1000 us waveform) Output (Battery Operation) Voltage Voltage Regulation Frequency 80-138 vac (160-274) 700VA 1000VA 500W Rack Mount unit w/ one external battery Rack Mount unit w/ two external battery Rack Mount unit w/ three external battery Rack Mount unit w/ four externa
English CONFIGURABLE PARAMETERS AND SETTINGS (These items may require optional software or hardware) FUNCTION FACTORY DEFAULT USER CHOICES DESCRIPTION UPS ID MCP-E SERIES Up to 64 characters to define the UPS Use this function to uniquely identify the UPS in your network configuration Battery installation date Date of Manufacture Date of Battery Replacementday/month/year (xx/xx/xxxx) Enter the current date when replacing the batteries Battery life in days Preset for 1826 days Enter up to 5 charac
The MCP-E series UPS has a replacable receptacle panel. The receptacle panel can be configured with multiple choices of receptacles. This will allow the user to customize the output receptacles for their specific applications. MINUTEMAN will only use UL or CE approved receptacles. To customize your MINUTEMAN UPS for your specific application, contact your local distributor or contact MINUTEMAN at 972-446-7363, 800-238-7272 or fax 972-446-9011 to find out which opitions are available.
LIMITED PRODUCT WARRANTY English LIMITED PRODUCT WARRANTY Para Systems Inc. (Para Systems) warrants this equipment, when properly applied and operated within specified conditions, against faulty materials or workmanship for a period of three years from the date of purchase. For equipment sites within the United States and Canada, this warranty covers repair or replacement of defective equipment at the discretion of Para Systems. Repair will be from the nearest authorized service center.
English DECLARATION OF CONFORMITY Application of Council Directive(s): 89/336/EEC, 7/23/EEC Standard(s) to which Conformity is declared: EN50091-1, EN50091-2, EN60555-2, EN61000-3 Manufacturer’s Name: Para Systems, Inc.
English Notes: 30 32
Para Systems, Inc. 1455 Lemay Dr. Carrollton, TX 75007 Phone: 972-446-7363 800-238-7272 Fax: 972-446-9011 Quickfax: 800-263-3933 Internet: minutemanups.