Specifications

Neatly installed with pericover concealed.
Easy installation in perimeter zone.
PFFY-P VLRM-E
PFFY-P VLRMM-E
INDOOR UNIT
Floor mounted concealed type
The body is concealed in the pericover to pursue harmony with the interior.
The compact body of 220mm(8-11/16in.) in depth can be easily installed in the
perimeter zone.
Compact unit for easy air conditioning in perimeter zone.
Optimum dehumidification depending on indoor temperature to prevent over-cooling.
Refreshing dehumidification can be attained.
Electronics dry function dehumidify refreshingly to prevent over-cooling.
The additional external static pressure capacity provides flexibility for duct
extension, branching, and air outlet configuration.
Maximum external static pressure 60Pa (VLRMM model)
SA
RA
installation image
(PFFY-P VLRMM-E)
Specifications
Notes:
*1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling Indoor : 27°C(81°F)DB/19°C(66°F)WB, Outdoor 35°C(95°F)DB
Heating Indoor : 20°C(68°F)DB, Outdoor 7°C(45°F)DB/6°C(43°F)WB
*2 Air flow rate/Sound pressure level are in (Low-High)
*3 Measured point : 1m x 1m, Power supply : AC240V/50Hz
·
1dB(A) lower at AC230V/50Hz
·
2dB(A) lower at AC220V/50Hz
·
3dB(A) lower at 1.5m x 1.5m point
*4 It is measured in anechoic room.
Notes:
*1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling Indoor : 27°C(81°F)DB/19°C(66°F)WB, Outdoor 35°C(95°F)DB
Heating Indoor : 20°C(68°F)DB, Outdoor 7°C(45°F)DB/6°C(43°F)WB
pipe length : 7.5m(24-9/16ft) Height difference : 0m(0ft)
*2 The external static pressure is set to 20Pa at factory shipment.
Power source
Cooling capacity
Heating capacity
Power
consumption
Current
External finish(Munsell No.)
Dimension H x W x D
Net weight
Heat exchanger
Fan
Motor
Air filter
Refrigerant
pipe diameter
Field drain pipe diameter
Sound pressure
level (Lo-Mid-Hi)
*3
Gas
Liquid
20Pa
40Pa
60Pa
Type x Quautity
Airflow rate
(Lo-Mid-Hi)
External static pressure
Type
Output
Cooling
Heating
Cooling
Heating
kW
BTU/h
kW
BTU/h
kW
kW
A
A
mm
in.
kg(lbs.)
m
3
/min
L/s
cfm
Pa
kW
mm(in.)
mm(in.)
mm(in.)
dB(A)
dB(A)
dB(A)
*1
*1
*1
*1
*
2
PFFY-P20VLRMM-E
0.04
0.04
0.34
0.34
639 x 886 x 220
25-3/16 x 34-15/16 x 8-11/16
18.5 (41)
Sirocco fan x 1
4.5-5.5-6.5
75-92-108
159-194-230
31-36-40
34-39-42
35-40-43
639 x 1,246 x 220
25-3/16 x 49-1/16 x 8-11/16
PFFY-P25VLRMM-E PFFY-P32VLRMM-E
3.6
12,300
4.0
13,600
0.04
0.04
0.38
0.38
20 (45)
6.5-7.5-9.0
108-125-150
230-265-318
27-32-37
30-35-41
32-37-42
2.2
7,500
2.5
8,500
2.8
9,600
3.2
10,900
PFFY-P40VLRMM-E
4.5
15,400
5.0
17,100
0.05
0.05
0.43
0.43
21 (47)
8.0-9.5-11.0
133-158-183
282-335-388
30-36-40
32-38-42
3.5-39-44
PFFY-P50VLRMM-E
5.6
19,100
6.3
21,500
0.05
0.05
0.48
0.48
25 (56)
10.0-12.0-14.0
167-200-233
353-424-494
32-37-41
35-40-44
36-41-45
PFFY-P63VLRMM-E
7.1
24,200
8.0
27,300
0.07
0.07
0.59
0.59
27 (60)
11.0-13.0-15.5
183-217-258
388-459-547
ø15.88 (ø5/8) Brazed
ø9.52 (ø3/8) Brazed
35-40-44
36-42-47
38-43-48
1-phase 220-240V 50Hz / 1-phase 220-240V 60Hz
Galvanized steel plate
639 x 1,006 x 220
25-3/16 x 39-5/8 x 8-11/16
Cross fin (Aluminum plate fin and copper tube)
20/40/60
DC motor
0.096
PP Honeycomb fabric (washable)
ø12.7 (ø1/2) Brazed
ø6.35 (ø1/4) Brazed
I.D.26 (1) <Accessory hose O.D.27 (1-3/32) (top end :20 (13/16))>
Sirocco fan x 2
Power source
Cooling capacity
Heating capacity
Power
consumption
Current
External finish(Munsell No.)
Dimension H x W x D
Net weight
Heat exchanger
Fan
Motor
Air filter
Refrigerant
pipe diameter
Field drain pipe diameter
Sound pressure level
(Lo-Hi) *2 *3 *4
Gas
(Flare)
Liquid
(Flare)
Type x Quautity
Airflow rate
(Lo-Hi)
External static pressure
Type
Output
Cooling
Heating
Cooling
Heating
kW
BTU/h
kW
BTU/h
kW
kW
A
A
mm
in.
kg(lbs.)
m
3
/min
L/s
cfm
Pa
kW
mm(in.)
mm(in.)
mm(in.)
dB(A)
*1
*1
*1
*1
*2
PFFY-P20VLRM-E
2.2
7,500
2.5
8,500
ø12.7 (ø1/2)
ø6.35 (ø1/4)
0.04 / 0.06
0.04 / 0.06
0.19 / 0.25
0.19 / 0.25
639 x 886 x 220
25-3/16 x 34-15/16 x 8-11/16
18.5 (41)
Sirocco fan x 1
5.5-6.5
92-108
194-230
0.015
34-40
639 x 1,246 x 220
25-3/16 x 49-1/16 x 8-11/16
PFFY-P25VLRM-E
2.8
9,600
3.2
10,900
PFFY-P32VLRM-E
3.6
12,300
4.0
13,600
0.06 / 0.07
0.06 / 0.07
0.29 / 0.30
0.29 / 0.30
20 (45)
7.0-9.0
117-150
247-318
0.018
35-40
PFFY-P40VLRM-E
4.5
15,400
5.0
17,100
0.065 / 0.075
0.065 / 0.075
0.32 / 0.33
0.32 / 0.33
21 (47)
9.0-11.0
150-183
318-388
0.030
PFFY-P50VLRM-E
5.6
19,100
6.3
21,500
0.085 / 0.09
0.085 / 0.09
0.40 / 0.41
0.40 / 0.41
25 (56)
12.0-14.0
200-233
424-494
0.035
PFFY-P63VLRM-E
7.1
24,200
8.0
27,300
0.1 / 0.11
0.1 / 0.11
0.46 / 0.47
0.46 / 0.47
27 (60)
12.0-15.5
200-258
424-547
0.050
ø15.88 (ø5/8)
ø9.52 (ø3/8)
40-46
1-phase 220-240V 50Hz / 1-phase 208-230V 60Hz
Galvanized steel plate
639 x 1,006 x 220
25-3/16 x 39-5/8 x 8-11/16
Cross fin (Aluminum plate fin and copper tube)
0
1-phase induction motor
PP Honeycomb fabric (washable)
I.D.26 (1) <Accessory hose O.D.27 (1-3/32) (top end :20 (13/16))>
Sirocco fan x 2
38-43