Specifications

In addition to the automatic damper open/close function,
open/close control via external devices is now possible,
delivering a “By-pass” ventilation system that is suitable
to the installed environment.
· Temperature sensor
· Humidity sensor
· Timers
"By-pass" operation
New function: "By-pass" Ventilation External Control Setting
* When the outdoor air tempereture drops lower than 8°C
it changes to the heat
exchange ventilation. (Display of the remote controller does not change.)
* In the case of
“By-pass” ventilation, the supply air temperature slightly rises more
than the outside air temperature because of the heat effect around the ducts or the
unit motors.
Automatic ventilation setting
The automatic damper mode automatically provides
the correct ventilation for the conditions in the room.
The following shows the effect “By-pass” ventilation will
have under various conditions.
1. Reduces cooling load
If the air outside is cooler than the air inside the
building during the cooling season (such as early
morning or at night), “By-pass” ventilation will draw
in the cooler outside air and reduce the cooling load
on the system.
2. Night purge
“By-pass” ventilation can be used to release hot air
from inside the building that has accumulated in
buildings a business district during the hot summer
season.
3. Office equipment room cooling
During cold season, fresh air can be drawn in and
used as is to cool rooms where the temperature has
risen due to the use of office equipment.
Establish the wire connection by inserting the optional
remote display adaptor (PAC-SA88HA-E) in the connector
CN16 (Ventilation mode selector).
With SW1 is “ON”, the ventilation mode of LOSSNAY is
changed to the By-pass ventilation regardless of the
setting on the remote controller.
Control devices (example)
SW1
CN16
SW1: By-pass ventilation operation switch
(When closed: For By-pass ventilation operation)
Remote display adaptor
(Optional) PAC-SA88HA-E
Brown 1
Red 2
Green 5
Not used. Insulate completely
LOSSNAY
control board
Fan speed/
entilation
mode selection
Max wiring length 10 m
Damper
LOSSNAY core
Fresh air
Supply air
Exhaust air
Return air
New Remote Controller PZ-60DR-E
A new remote controller for the RX5 series is now available. In addition to boosting the energy conservation perfor-
mance of the main unit, the remote controller features a variety of new functions which also pursue additional energy
conservation.
The appearance of the remote controller conforms to Mitsubishi air conditioner interface design standards.
Functions that were set using Dip-
Switch on the LOSSNAY main unit
can now be configured as needed
using the new remote controller.
This eliminates the need to crawl
under the eaves to change operation
settings.
Also, a newly adopted dot matrix
display provides much more informa-
tion, making it easy to check mainte-
nance indications, operation status
display, and explanations required
when configuring settings.
Dot matrix display
Button
FILTER button
"Extra Low" fan speed button
OPERATION button
ON/OFF button
Fti ltbtt
OPERATION buttons
Back Ahead
Fan speed Adjustment button
CLEAR button
Timer MENU (MONITOR/SET) button
Return button
Orange 3
Yellow 4
Model line up
Specification
LGH-15RX
5
-E
LOSSNAY ventilation By-pass ventilation
Extra High High Low Extra Low
0.44-0.46
96-110
150
42
10.2-10.7
100-105
82.0
75.0
73.0
27.5-28
0.37-0.38
80-90
150
42
6.6-7.1
65-70
82.0
75.0
73.0
26.5-27
0.25-0.25
53-59
110
31
3.6-4.1
35-40
84.0
77.5
76.5
22-23.5
0.14-0.15
30-35
70
19
1.4
14
85.5
81.0
81.0
18
Extra High High Low Extra Low
0.45-0.46
97-110
150
42
10.2-10.7
100-105
28.5-29
0.37-0.38
81-91
150
42
6.6-7.1
65-70
27-28
0.25-0.26
54-61
110
31
3.6-4.1
35-40
23-24
0.14-0.15
30-35
70
19
1.4
14
18-19
20
Under 0.8 A Less
*The Air outlets noise (45 angle, 1.5 meters in front of the unit) is about 6 dB greater than the indicated value. (at High Fan speed)
50Hz / Single phase 220-240V
Ventilation mode
Fan speed
Current
(
A
)
Power consumption
(
W
)
Air volume
Model
External static pressure
Temperature exchange efficiency
(
%
)
Enthalpy exchange efficiency
(
%
)
Noise
(
dB
)
(
Measured at 1.5m under the center
of panel in an anechoeic chamber)
Weight
(
kg
)
Starting current
(
m
3
/h
)
(
L/s
)
(
mmH
2O
)
(
Pa
)
Heating
Cooling
LGH-25RX
5-E
LOSSNAY ventilation By-pass ventilation
Extra High High Low Extra Low
0.52-0.55
113-129
250
69
8.2-8.7
80-85
79.0
69.5
68.0
26-27
0.47-0.48
102-114
250
69
5.1-6.1
50-60
79.0
69.5
68.0
25-26
0.26-0.27
56-62
155
43
2-2.5
20-25
81.5
74.0
72.5
20-21.5
0.17-0.18
36-42
105
29
0.9
9
83.5
77.5
76.0
18-19
Extra High High Low Extra Low
0.53-0.55
115-131
250
69
8.2-8.7
80-85
26.5-27.5
0.47-0.48
103-115
250
69
5.1-6.1
50-60
25.5-26.5
0.26-0.27
56-63
155
43
2-2.5
20-25
20.5-22
0.17-0.18
36-42
105
29
0.9
9
18-19
20
Under 0.9 A Less
*The Air outlets noise (45 angle,1.5 meters in front of the unit) is about 10 dB greater than the indicated value. (at High Fan speed)
Frequency / Power source
50Hz / Single phase 220-240V
Ventilation mode
Fan speed
Current
(
A
)
Power consumption
(
W
)
Air volume
Model
External static pressure
Temperature exchange efficiency
(
%
)
Enthalpy exchange efficiency
(
%
)
Noise
(
dB
)
(
Measured at 1.5m under the center
of panel in an anechoeic chamber)
Weight
(
kg
)
Starting current
(
m
3
/h
)
(
L/s
)
(
mmH
2O
)
(
Pa
)
Heating
Cooling
LGH-35RX
5-E
LGH-35RX5-E
LOSSNAY ventilation By-pass ventilation
Extra High High Low Extra Low
0.92-0.92
195-212
350
97
15.8-16.3
155-160
80.0
71.5
71.0
32-32
0.74-0.74
160-169
350
97
7.6-8.2
75-80
80.0
71.5
71.0
28.5-29.5
0.5-0.51
105-116
210
58
2.5-3.1
25-30
85.0
76.5
75.5
21.5-23
0.28-0.3
58-69
115
32
0.9
9
88.0
81.5
81.0
18
Extra High High Low Extra Low
0.93-0.94
197-217
350
97
15.8-16.3
155-160
32.5-32.5
0.77-0.77
164-173
350
97
7.6-8.2
75-80
29.5-30.5
0.51-0.52
105-116
210
58
2.5-3.1
25-30
21.5-24
0.28-0.3
58-69
115
32
0.9
9
18
29
Under 2.4 A Less
*The Air outlets noise (45 angle, 1.5 meters in front of the unit) is about 10 dB greater than the indicated value. (at High Fan speed)
Frequency / Power source
50Hz / Single phase 220-240V
LGH-25RX5-E
LGH-15RX5-E
Frequency / Power source
Ventilation mode
Fan speed
Current
(
A
)
Power consumption
(
W
)
Air volume
Model
External static pressure
Temperature exchange efficiency
(
%
)
Enthalpy exchange efficiency
(
%
)
Noise
(
dB
)
(
Measured at 1.5m under the center
of panel in an anechoeic chamber)
Weight
(
kg
)
Starting current
(
m
3
/h
)
(
L/s
)
(
mmH
2O
)
(
Pa
)
Heating
Cooling
LGH-15~100RX5-E