Specifications

Control
The New Remote Controller PZ-60DR-E enable simple control setting
Centralized Controller System
LOSSNAY independent
Interlocked with Air conditioners
Interlocked with City Multi Interlocked with Mr.Slim
City Multi
M-NET transmission line
Mr.Slim LOSSNAY
RX
5
LOSSNAY
RX
5
Slim-LOSSNAY connection cable
LOSSNAY remote
controller
PZ-60DR-E
LOSSNAY remote
controller
PZ-60DR-E
can be connected
LOSSNAY RX
5
(Max 15 unit)
PZ-52SF-E can be used insted of PZ-60DR-E,
However, function is limited and connecting
position is different.
The LOSSNAY remote controller (PZ-60DR-E,
PZ-41SLB-E) can not be used with this system.
PZ-41SLB-E can be connected however function
is limited.
Centralized controller
AG-150A
Power supply unit
(PAC-SC51KUA)
Outdoor unit
Network remote
controller
Network remote
controller
LOSSNAY
RX
5
LOSSNAY remote
controller
PZ-60DR-E
Interlocked with
CITY MULTI indoor units
Interlocked with
Mr. Slim indoor units
LOSSNAY units only
Interlocked with
external devices
Indoor unit Indoor unit
LOSSNAY remote
controller
PZ-60DR-E
LOSSNAY
RX
5
Ext. signal source
LOSSNAY remote
controller
PZ-60DR-E
LOSSNAY remote
controller
PZ-60DR-E
LOSSNAY
RX
5LOSSNAY
RX
5
MSli
Mr.Slim
outdoor unit
M-NET
adapter
Mr.Slim
indoor unit
LOSSNAY
RX
5
Time Spent in Comfort with a Breath of Fresh Air
Specification
Optional parts
Total-Heat-Exchange Concept
Heat Recovery Ventilators for Residential Use
VL-100U-E
Energy Saving
Reduced heat loss
contributes to
lower air
conditioning
costs.
Quiet
Operation
Super sound
insulation
and quiet
operation.
Fresh Air
Simultaneous air
supply/exhaust
function ensures that
air stays fresh
with efficient
ventilation.
Simple
Installation
Easy Installation
through boring
of 2 installation
holes.
•Heat-exchange calculating equation
Indoor supply-air
temperature(
°C
)
Calculation example : 15.4
°C
= (20
°C
- 0
°C
) x 77% + 0
°C
(Low notch)
Indoor
temperature(
°C
)
Outdoor
temperature(
°C
)
Outdoor
temperature(
°C
)
Temp exchange
efficiency(%)
=
{}
-+x
•Heat-exchange calculating equation
Indoor supply-air
temperature(
°C
)
Calculation example : 35
°C
= (35
°C
- 21
°C
) x 77% (Low notch)
Indoor
temperature(
°C
)
Outdoor
temperature(
°C
)
Outdoor
temperature(
°C
)
Temp exchange
efficiency(%)
=
}
-+
{
x
operation
in Winter
operation
in Summer
20°C
Stale warm air
(indoor air)
15.4°C
Fresh warm air
(indoor supply air)
0°C
Fresh cool air
(outdoor air)
4.6°C
Stale hot air
(exhasut)
21°C
Stale cool air
(indoor air)
24.2°C
Fresh cool air
(indoor supply air)
35°C
Fresh hot air
(outdoor air)
31.8°C
Stale cool air
(exhasut)
•Simple installation through boring of 2 installation holes.
•Low-noise(Less than 30dB at low notch).
•1-motor 2-fan system. •Air-volume:low/high 2-notch.
•Air-supply/exhaust pipes and plastic weather cover are
supplied as accessories.
•Equipped with an outdoor-air shutter. •Pull-string switch
Notch
Supply
Voltage
(V)
220-240
220
Power line
frequency
(Hz)
50
60
Temp.exchange
efficiency
(%)
Power
Consumption
(W)
Noise
(dB)
Air volume
(m
3
/h)
Weight
(kg)
70
77
73
80
HI
LO
HI
LO
26
23
26
21
39
29.5
37
26
105
65
90
50
6.5
Outer diameter ø75
Inner diameter ø70
280
ø
75
ø
70
60
2020
ø
79
M75
Extension Pipe
P-100P
Extension Pipe Coupling
P-100PJ
SA
OA
EA
RA