Twinning on the outdoor unit side
See the following drawing for connecting the pipes between the outdoor units.
CAUTION
The length of the straight pipe must be 500mm [19 in.] or longer.
If not, it may cause improper operation.
Field piping
Field piping
Twinning kit
The length of the straight pipe
must be 500 mm [19 in.]
or longer
<PUHY-P500YSHA>