Specifications

1. Specifications
(1) Standard type
5
!!. Indoor Unit
Model Name
Indoor PFAV-P250VM-E
Outdoor
PUHY-P250YHA(-BS)
Cooling
Heating
Cooling
Heating
System capacity
kW
kW
kW
kW
Cooling
Heating
25.0 (Maximum28.0)
28.0 (Maximum 31.5)
System Power input
7.46 / 7.53
8.27 / 8.34
System current
A
A
14.5-13.8-13.3 / 13.4-12.8-12.3
15.8-15.0-14.4 / 14.7-14.0-13.4
Power source 3-phase 4-wire 380-400-415V (50Hz / 60Hz)
Power input kW 0.82 / 0.89
Current A 3.4-3.2-3.1 / 2.3-2.2-2.1
Fan
Type x Quantity Sirocco fan x 2
Airflow rate
m /min
3
90
External static pressure Pa 30 / 90
Motor output kW 2.2
Refrigerant R410A
External finish
External dimension mm
1748(H) x 1200(W) x 485(D)
Protection devices Fan Thermal switch
Refrigerant
piping diameter
mm
mm
Liquid pipe
9.52 Brazed (12.7 for over 90m)
Gas pipe 22.2 Brazed
Refrigerant piping allowable length
m 165
Sound pressure level dB(A) 55
Heat exchanger Cross fin (aluminum plate fin and copper tube)
Air filter Synthetic fiber unwoven cloth filter
Net weight kg 156
Operating
temperature range
Cooling
Heating
PFAV-P500VM-E
PUHY-P500YSHA(-BS)
(PUHY-P250YHA(-BS) x 2,
CMY-Y100VBK2)
50.0 (Maximum56.0)
56.0 (Maximum 63.0)
17.85 / 18.84
17.00 / 17.99
32.3-30.7-29.6 / 32.6-31.0-29.9
30.8-29.3-28.2 / 31.1-29.6-28.5
2.37 / 3.36
6.2-5.9-5.7 / 6.5-6.2-6.0
Sirocco fan x 1
180
30 / 130
5.5
R410A
Galvanized steel plate (with polyester coating)
MUNSELL 5Y 8 / 1 or similar
1899(H) x 1420(W) x 635(D)
Thermal switch
15.88 Brazed
28.58 Brazed
165
59 / 62
265
Indoor: 10 to 25 ˚CWB
Indoor: 15 to 28 ˚CDB
(Outdoor: -5 to 43 ˚CDB)
(Outdoor: -20 to 15.5 ˚CWB)
PFAV-P750VM-E
PUHY-P750YSHA(-BS)
(PUHY-P350YHA(-BS) +
PUHY-P400YHA(-BS),
CMY-Y200VBK2)
71.0 (Maximum 80.0)
80.0 (Maximum 90.0)
26.33 / 27.40
23.93 / 25.00
48.1-45.7-44.1 / 47.5-45.1-43.5
43.4-41.2-39.8 / 42.8-40.6-39.2
4.30 / 5.37
10.9-10.4-10.0 / 10.3-9.8-9.4
Sirocco fan x 1
260
100 / 310
7.5
R410A
1860(H) x 1750(W) x 1064(D)
Thermal switch
19.05 Brazed
34.93 Brazed
165
65
PP Honeycomb fabric filter
459
Note
1. Cooling / Heating capacity indicates the maximum value at operation under the following conditions.
(Cooling) Indoor: 27˚CDB / 19˚CWB, Outdoor: 35˚CDB
(Heating) Indoor: 20˚CDB, Outdoor: 7˚CDB / 6˚CWB
Pipe length: 7.5m, Level difference: 0m
2. The sound pressure level is measured in an anechoic room.
3. Long period operation in a high temperature and humidity atmosphere (dew point of 23
˚C or more) may cause
condensation.
4. Works not included: Installation / foundation work, electric connection work, duct work, insulation work.
The power source switch and other items are not specified in the specifications.