Specifications

6
Model Name
Indoor PFAV-P300VM-E-F
Outdoor
PUHY-P250YHA(-BS)
Cooling
Heating
Cooling
Heating
System capacity
kW
kW
kW
kW
Cooling
Heating
28.0 (Maximum 33.5)
26.5 (Maximum 28.0)
System Power input
6.73 / 6.72
7.57 / 7.56
System current
A
A
12.6-11.9-11.5 / 12.2-11.5-11.1
14.0-13.3-12.8 / 13.6-12.9-12.4
Power source 3-phase 4-wire 380-400-415V (50Hz / 60Hz)
Power input kW 0.37 / 0.36
Current A 1.9-1.8-1.7 / 1.5-1.4-1.3
Fan
Type x Quantity Sirocco fan x 2
Airflow rate
m /min
3
45
External static pressure Pa 80
Motor output kW 1.5
Refrigerant R410A
External finish
External dimension mm
1748(H) x 1200(W) x 485(D)
Protection devices Fan Thermal switch
Refrigerant
piping diameter
mm
mm
Liquid pipe
9.52 Brazed (12.7 for over 90m)
Gas pipe 22.2 Brazed
Refrigerant piping allowable length
m 165
Sound pressure level dB(A) 48.5
Heat exchanger Cross fin (aluminum plate fin and copper tube)
Air filter Synthetic fiber unwoven cloth filter
Net weight kg 151
Operating
temperature range
Cooling
Heating
PFAV-P600VM-E-F
PUHY-P500YSHA(-BS)
(PUHY-P250YHA(-BS) x 2,
CMY-Y100VBK2)
56.0 (Maximum 67.0)
50.0 (Maximum 56.0)
14.69 / 15.05
15.43 / 15.79
26.1-24.9-24.0 / 26.2-25.0-24.0
27.4-26.1-25.1 / 27.5-26.2-25.1
0.90 / 1.26
2.9-2.8-2.8 / 3.0-2.9-2.8
Sirocco fan x 1
90
110 / 170
2.2
R410A
Galvanized steel plate (with polyester coating)
MUNSELL 5Y 8 / 1 or similar
1899(H) x 1420(W) x 635(D)
Thermal switch
15.88 Brazed
28.58 Brazed
165
50 / 53
248
Indoor: 15 to 35 ˚CWB
Indoor: 0 to 20 ˚CDB
(Outdoor: 20 to 43 ˚CDB)
(Outdoor: -4 to 15.5 ˚CWB)
PFAV-P900VM-E-F
PUHY-P750YSHA(-BS)
(PUHY-P350YHA(-BS) +
PUHY-P400YHA(-BS),
CMY-Y200VBK2)
80.0 (Maximum 100.0)
71.0 (Maximum 80.0)
22.54 / 22.74
21.43 / 21.63
40.5-38.5-37.1 / 39.6-37.6-36.2
38.7-36.8-35.5 / 37.8-35.9-34.6
1.77 / 1.97
5.6-5.3-5.1 / 4.7-4.4-4.2
Sirocco fan x 1
120
210 / 330
3.7
R410A
1860(H) x 1750(W) x 1064(D)
Thermal switch
19.05 Brazed
34.93 Brazed
165
57
PP Honeycomb fabric filter
437
Note
1. Cooling / Heating capacity indicates the maximum value at operation under the following conditions.
(Cooling) Indoor,Outdoor: 33˚CDB / 28˚CWB
(Heating) Indoor,Outdoor: 7˚CDB / 3˚CWB
Pipe length: 7.5m, Level difference: 0m
2. The sound pressure level is measured in an anechoic room.
3. The indoor intake air temperature should be kept more than 0 ˚C.
4. At factory setting, the fan temporary stops in defrosting. Change DIP SW for fan to operate in defrosting.
5. Indoor temperature and humidity cannnot be controlled with Fresh air intake type.
6. Works not included: Installation / foundation work, electric connection work, duct work, insulation work.
The power source switch and other items are not specified in the specifications.
(2) Fresh air intake type