Instruction manual

PARAMETERS
147
Pr. 76 "alarm code output selection"
Pr. 79 "operation mode selection"
Related parameters
Programmed operation function (Pr. 200 to Pr. 231)
Pr. 200 "program minute/second selection"
Pr. 201 to Pr. 210 "program setting 1 to 10"
Pr. 211 to Pr. 220 "program setting 11 to 20"
Pr. 221 to Pr. 230 "program setting 21 to 30"
Pr. 231 "time-of-day setting"
In programmed operation, automatic operation is performed under the control of the internal timer in
accordance with the preset time of day, running frequency and rotation direction.
This function is made valid when the following parameter is set to the following value:
·
Pr. 79 = "5" (programmed operation)
You can select the time unit for programmed operation between "minute/second" and "hour/minute".
The start time of day, rotation direction and running frequency are defined as one point and every 10 points
are grouped into three:
·
Group 1: Pr. 201 to Pr. 210
·
Group 2: Pr. 211 to Pr. 220
·
Group 3: Pr. 221 to Pr. 230
Use Pr. 231 to set the time of day when programmed operation is started.
Parameter
Number
Factory
Setting
Setting Range Remarks
200 0 0 to 3
0, 2 [minute/second]
1, 3 [hour/minute]
201 to 210 0,9999,0
0 to 2
0 to 400, 9999
0 to 99.59
0 to 2: Rotation direction
0 to 400, 9999: Frequency
0 to 99.59: Time
211 to 220 0,9999,0
0 to 2
0 to 400, 9999
0 to 99.59
0 to 2: Rotation direction
0 to 400, 9999: Frequency
0 to 99.59: Time
221 to 230 0,9999,0
0 to 2: Rotation direction
0 to 400, 9999: Frequency
0 to 99.59: Time
0 to 2: Rotation direction
0 to 400, 9999: Frequency
0 to 99.59: Time
231 0 0 to 99.59
<Wiring example>
·
For sink logic
STF
RH
RM
RL
STR
SD
FU
OL
PF
SU
SE
I
1
2
3
U,V,W
Output signal common
Programmed
operation start
Group selection
T
imer reset
Input signal common
Inverter
Motor
Terminal function Pr. 79 = 5
Terminal function Pr. 76 = 3
Group run signals
(Open collector)
Time-out signal
R,S,T
L
1
,L
2
,L
3