Instruction manual

PARAMETERS
163
Frequencies set in stop-on-contact control (Pr. 270 = 1 or 3) (In external operation mode)
The following table lists the frequencies set when the input terminals (RH, RM, RL, RT, JOG) are selected
together.
Input Signals
RH RM RL RT JOG
Set Frequency
Stop-on-
Contact
Control
Function
Remarks
Speed 1 (high speed) Pr. 4
Speed 2 (middle speed) Pr. 5
Speed 3 (low speed) Pr. 6
According to 0-5V, 0-10V, 4-20mA
Jog frequency Pr. 15
Speed 6 Pr. 26
Middle speed when
Pr. 26 = 9999
Speed 5 Pr. 25 Low speed when Pr. 25 = 9999
Speed 1 (high speed) Pr. 4
Jog frequency Pr. 15
Speed 4 Pr. 24 Low speed when Pr. 24 = 9999
Speed 2 (middle speed) Pr. 5
Jog frequency Pr. 15
Speed 3 (low speed, stop-on-contact
frequency) Pr. 6
Jog frequency Pr. 15
Jog frequency Pr. 15
Jog frequency Pr. 15
Jog frequency Pr. 15
Jog frequency Pr. 15
Speed 3 (low speed, stop-on-contact
frequency) Pr. 6
Jog frequency Pr. 15
Jog frequency Pr. 15
Speed 3 (low speed, stop-on-contact
frequency) Pr. 6
Jog frequency Pr. 15
Speed 6 Pr. 26
Middle speed when
Pr. 26 = 9999
Speed 7 Pr. 27 Low speed when Pr. 27 = 9999
Jog frequency Pr. 15
Jog frequency Pr. 15
Jog frequency Pr. 15
Jog frequency Pr. 6
Speed 3 (low speed, stop-on-contact
frequency) Pr. 6
Jog frequency Pr. 15
According to 0-5V, 0-10V, 4-20mA
* indicates that the function is selected.
Note: 1. indicates that the signal is on.
2. Indicates that the remote setting function is not selected. (The remote setting function disables
stop-on-contact control.)
3. The selection of the 12-bit digital speed input FR-A5AX (option) makes the above list invalid.
Note that when both RL and RT are on, the frequency is as set in Pr. 6 and stop-on-contact
control is exercised.
4. The jog frequency has the highest priority.
5. When the terminal functions are changed using Pr. 180 to Pr. 186, the other functions may be
affected. Confirm the functions of the corresponding terminals before making settings.