Instruction manual

PARAMETERS
61
Func-
tion
Parameter
Number
Name Setting Range
Minimum
Setting
Increments
Factory Setting
EC Version
Refer
To
Page:
200
Programmed operation minute/second
selection
0, 2: Minute, second
1, 3: Hour, minute
1 0 147
201
Program set 1
1 to 10
0-2: Rotation direction
0-400, 9999: Frequency
0-99.59: Time
1
0.1Hz
Minute or
second
0
9999
0
147
211
Program set 2
11 to 20
0-2: Rotation direction
0-400, 9999: Frequency
0-99.59: Time
1
0.1Hz
Minute or
second
0
9999
0
147
221
Program set 3
21 to 30
0-2: Rotation direction
0-400, 9999: Frequency
0-99.59: Time
1
0.1Hz
Minute or
second
0
9999
0
147
Programmed operation
231
Timer setting 0 to 99.59

0 147
232
Multi-speed setting (speed 8) 0 to 400Hz, 9999 0.01Hz 9999 151
233
Multi-speed setting (speed 9) 0 to 400Hz, 9999 0.01Hz 9999 151
234
Multi-speed setting (speed 10) 0 to 400Hz, 9999 0.01Hz 9999 151
235
Multi-speed setting (speed 11) 0 to 400Hz, 9999 0.01Hz 9999 151
236
Multi-speed setting (speed 12) 0 to 400Hz, 9999 0.01Hz 9999 151
237
Multi-speed setting (speed 13) 0 to 400Hz, 9999 0.01Hz 9999 151
238
Multi-speed setting (speed 14) 0 to 400Hz, 9999 0.01Hz 9999 151
Multi-speed operation
239
Multi-speed setting (speed 15) 0 to 400Hz, 9999 0.01Hz 9999 151
240
Soft-PWM setting
0, 1
1 1 151
Sub functions
244
Cooling fan operation selection
0, 1
1 0 151
Stop selection
function
250
Stop selection 0 to 100 s, 9999 0.1 s 9999 152
251
Output phase failure protection selection 0,1
1 1 153
252
Override bias 0 to 200%
0.1% 50% 153
Additional
function
253
Override gain 0 to 200%
0.1% 150% 153
261
Power failure stop selection 0, 1
1 0 154
262
Subtracted frequency at deceleration
start
0 to 20Hz
0.01Hz 3Hz 154
263
Subtraction starting frequency 0 to 120Hz, 9999
0.01Hz 60Hz
50Hz
154
264
Power-failure deceleration time 1 0 to 3600/0 to 360 s 0.1 s/0.01 s 5 s
154
265
Power-failure deceleration time 2
0 to 3600/0 to 360 s,
9999
0.1 s/0.01 s
9999 154
Power failure stop function
266
Power-failure deceleration time switch-
over frequency
0 to 400Hz
0.01Hz 60Hz
50Hz
154
Selection
function
270
Stop-on-contact/load torque high-speed
frequency control selection
0, 1, 2, 3 1 0 156
271
High-speed setting maximum current 0 to 200% 0.1% 50% 157
272
Mid-speed setting minimum current 0 to 200% 0.1% 100% 157
273
Current averaging range 0 to 400Hz, 9999 0.01Hz 9999 157
High-speed
frequency
control
274
Current averaging filter constant 1 to 4000 1 16 157
275
Stop-on-contact exciting current low-
speed multiplying factor
0 to 1000%, 9999 1% 9999 (Note 5) 161
Stop on
contact
276
Stop-on-contact PWM carrier frequency 0 to 15, 9999 1 9999 (Note 5) 161
Parameter List