Automatic restart after instantaneous power failure (Pr. 57, Pr. 58, Pr. 162 to Pr. 165)
Pr. 57 "coasting time for automatic restart after instantaneous power
failure/commercial power supply-inverter switch-over"
Pr. 58 "cushion time for automatic restart after instantaneous power
failure/commercial power supply-inverter switch-over"
Pr.162 "Automatic restart after instantaneous power failure selection"
Pr.163 "First cushion time for restart"
Pr.164 "First cushion voltage for restart"
Pr.165 "Restart stall prevention operation level"
You can restart the inverter without stopping the motor (with the motor coasting) when the commercial
power supply is switched to the inverter operation or when the power is restored after an instantaneous
power failure. (When automatic restart operation is set to be enabled, UVT and IPF among the alarm
output signals will not be output at occurrence of an instantaneous power failure.)
Parameter
Number
Factory Setting Setting Range Remarks
57 9999 0, 0.1 to 5 s, 9999 9999: No restart
58 1.0 s 0 to 60 s
162 0 0, 1
0: Frequency search, 1: No frequency
search
163 0 s 0 to 20 s
164 0% 0 to 100%
165 150% 0 to 200%
(Pr.163)
Pr.58
Pr.164
STF
IM
NFB
CS
SD
CS
SD
S1 L
21
R1
L
11
T L
3
S L
2
R L
1
MC1
MC2
×
MC3
W
V
U
Connect CS-SD for use of only
automatic restart after instantaneous
power failure.
Voltage
Time
Voltage rise time
MC switching sequence