(3) Wire the twisted pair shielded cable after stripping its sheath to make its cables loose.
Also, protect the shielded cable of the twisted pair shielded cable to ensure that it will not make contact
with the conductive area.
(4) Loosen the terminal screw and insert the cable into the terminal.
REMARKS
Information on bar terminals
Introduced products (as of August, 2005): Phoenix Contact Co.,Ltd.
Screw Size Tightening Torque Cable Size Screwdriver
M2 0.22Nm to 0.25Nm
0.3mm
2
to 0.75mm
2
Small flat-blade screwdriver
(Tip thickness: 0.4mm/tip width: 2.5mm )
CAUTION
Undertightening can cause cable disconnection or malfunction. Overtightening can cause a short circuit or
malfunction due to damage to the screw or unit.
Cable stripping size
Wire the stripped cable after twisting it to prevent it from becoming loose.
In addition, do not solder it.
Use a bar type terminal as required.
5mm
Bar terminal crimping tool: CRIMPFOX ZA3 (Phoenix Contact Co., Ltd.)
Terminal Screw
Size
Bar Terminal Model
(with insulation sleeve)
Bar Terminal Model
(without insulation sleeve)
Wire Size (mm
2
)
M2 Al 0.5-6WH A 0.5-6 0.3 to 0.5
When using the bar terminal (without insulation sleeve),