Specifications

17
WIRING
3
(3) Loosen the terminal screw and insert the cable into the terminal
according to the terminal arrignment.
Tighten each cable with fixing screws to the recommended tightening torque.
(4) Connect the terminal block to the connector for communication of the communication option mounted
on the inverter.
Screw Size
Tightening Torque
Cable Size Screwdriver
M3
0.5N•m to
0.6N•m
0.3mm
2
to
0.75mm
2
Small flat-blade screwdriver
(Tip thickness: 0.4mm/tip
width: 2.5mm)
CAUTION
Undertightening can cause cable disconnection or malfunction. Overtightening can cause a short
circuit or malfunction due to damage to the screw or unit.
V- (black)
CAN- (blue)
Shielded cable
CAN+ (white)
V+ (red)
Terminal layout
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1