Specifications

23
INVERTER SETTING
4
4.2.2 DeviceNet baud rate (Pr. 346)
Set baud rate etc. to start DeviceNet communication.
Parameter
Number
Name Setting Range
Minimum Setting
Increments
Initial
Value
346 DeviceNet baud rate 0 to 4095 1 132
Bit15 Bit14 Bit13 Bit12 Bit11 Bit10 Bit9 Bit8 Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
Baud Rate Key Input Assembly (IA) Output Assembly (OA)
Baud Rate
(BR)
Bit Item
Initial
Value
Setting Range Definition
0, 1 Baud Rate (BR) 0
0, 3 125kbps
This value can be set with DeviceNet
Object Class 0x03 Instance 1
Attribute 2.
(Refer to page 50)
1 250kbps
2 500kbps
2 to 6
Output
Assembly (OA)
1
0
Output Instance 20 (0x14)
· Set the same value for input
assembly and output assembly.
· The value can be set with Control
Supervisor Class 0x29 Instance 1
Attribute 140, 141. (Refer to page
69)
1
Output Instance 21 (0x15)
6
Output Instance 126 (0x7E)
Other than the above Output Instance 21 (0x15)
7 to 11
Input Assembly
(IA)
1
0
Input Instance 70 (0x46)
1
Input Instance 71 (0x47)
6
Input Instance 176 (0xB0)
Other than the above Input Instance 71 (0x47)
12 to 15 Baud Rate Key 0 0
Set "0" always. When a value other than "0" is set, the inverter
operates as when "132" (initial value) is set in Pr. 346.