Specifications

27
INVERTER SETTING
4
Pr. 340
Setting
Pr. 79
Setting
Operation Mode at Power on or Power
Restoration
Operation Mode Switchover
0
(initial
value)
0 (initial
value)
External operation mode
Switching among the external, PU, and NET operation mode is
enabled
*1
1 PU operation mode PU operation mode fixed
2 External operation mode
Switching between the external and Net operation mode is enabled
Switching to the PU operation mode is disallowed
3, 4 External/PU combined operation mode Operation mode switching is disallowed
6 External operation mode
Switching among the external, PU, and NET operation mode is
enabled while running.
7
X12 (MRS) signal ON ..... external operation mode Switching among the external, PU, and NET operation mode is enabled
*1
X12 (MRS) signal OFF ... external operation mode
External operation mode fixed (Forcibly switched to external
operation mode.)
1
0 NET operation mode
Same as when Pr. 340 = "0"
1 PU operation mode
2
NET operation mode
3, 4 External/PU combined operation mode
6
NET operation mode
7
X12 (MRS) signal ON .... NET operation mode
X12 (MRS) signal OFF ... external operation mode
10
0 NET operation mode Switching between the PU and NET operation mode is enabled *2
1 PU operation mode Same as when Pr. 340 = "0"
2
NET operation mode NET operation mode fixed
3, 4 External/PU combined operation mode Same as when Pr. 340 = "0"
6
NET operation mode
Switching between the PU and NET operation mode is enabled while
running
*2
7 External operation mode Same as when Pr. 340 = "0"
*1 Operation mode can not be directly changed between the PU operation mode and network operation mode.
*2 Operation mode can be changed between the PU operation mode and network operation mode with of the operation panel and
X65 signal.