OBJECT MAP
7.3.1 Output Instance 20/Input Instance 70
1. Output Instance 20 (Master→inverter)
When using Output Instance 20, set Input Instance to 70.
[Output Instance 20 details]
Byte Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
0 ⎯⎯⎯⎯⎯
Fault
Reset
⎯ Run Fwd
1 ⎯
2 Speed reference (low byte)
3 Speed reference (high byte)
Byte0
Bit0 Run Fwd
Forward rotation signal
(0:forward rotation off, 1:forward rotation on)
Bit2 Fault Reset
Reset request at an error occurrence
Valid only at in inverter trip
(0:no function, 1:fault reset request)
Byte2
Byte3
Speed Ref
Speed reference (r/min)
(Refer to page 42 for conversion formula of speed and frequency. )