Specifications

55
OBJECT MAP
7
2. Input Instance 71 (initial value) (Invertermaster)
When using Input Instance 71, set Output Instance to 21.
[Input Instance 71 details]
Byte Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
0
At
Reference
Ref From
Net
Ctrl From
Net
Ready
Running
Rev
Running
Fwd
Faulted
100
2 Speed actual (low byte)
3 Speed actual (high byte)
Byte0
Bit0 Faulted
Inverter error signal
(0:inverter is under normal operation 1: inverter is in a fault state)
Bit2 Running Fwd
Forward rotation (0: other than forward rotation, 1: forward rotation)
Bit3 Running Rev
Reverse rotation (0: other than reverse rotation, 1: reverse rotation)
Bit4 Ready
Ready signal (0: operation preparation, 1: operation ready)
(Always "1" after power on)
Bit5 CtrlFromNet
State of operation command source (Run/Stop)
(Same definition with Class 0x29 Instance 1 Attribute 15 Refer to page 69)
0: Command is enabled in operation other than network
1: Command is enabled in network operation
Bit6 RefFromNet
State of speed command source
(Same definition with Class 0x2A Instance 1 Attribute 29 Refer to page 71)
0: Command is enabled in operation other than network
1: Command is enabled in network operation
Bit7 AtReference
Up-to-frequency signal (SU signal)
(Same definition with Class 0x2A Instance 1 Attribute 3 Refer to page 70)
Byte2
Byte3
Speed Actual
Actual speed currently operating (r/min)
(Refer to page 42 for conversion formula of speed and frequency.)