Specifications

57
OBJECT MAP
7
[Output Instance 126 details]
Byte0
Bit0 Run Fwd
Forward rotation signal (0: forward rotation off, 1: forward rotation on)
Control related
signals
Makes valid when
NetCtrl (Bit5) = "1"
Bit1 Run Rev
Reverse rotation signal (0: reverse rotation off, 1: reverse rotation on)
Bit2 Fault Reset
Reset request at an error occurrence
Valid only at in inverter trip
(0:no function, 1:fault reset request)
Bit5 NetCtrl
Request permission bit of control related signals (Bit0 to Bit2)
0: Control related signals are invalid (It will not function even if a value is set in each bit.)
1: Control related signals are valid (It will not be reflected to Pr. 338.)
Bit6 NetRef
Request permission bit of speed reference (Byte 2, Byte 3)
0: Speed setting value (Byte 2, 3) is invalid (It will not function even if a value is set.)
1: Speed setting value (Byte 2, 3) is valid (It will not refflected to Pr. 339.)
Bit7 Write Param
Request permission bit of speed reference or parameter write (Byte 2, Byte 3)
0: Byte 2, 3 are speed reference
1: Byte 2, 3 are written to parameter write data (It is written to parameter class and attribute
set with Byte 4, 5.)
Byte1
Parameter
Instance No.
Parameter Instance No. can be specified.
When 00 is specified, instance No. is regarded as "1".
Byte2
Byte3
Speed Ref or
Parameter Write
Data
Speed reference (r/min) or parameter write data
Selection conditions are determined according to a
combination of "NetRef (Bit6)" and "WriteParam
(Bit7)".
[When speed reference is selected]
Refer to page
42 for conversion formula of speed
and frequency.
Byte4
Parameter
Class ID
Class ID to access to the inverter parameter (class 0x2A, 0x66, 0x67 etc.)
Byte5
Parameter
Attribute ID
Attribute ID to access to the inverter parameter
Write
Param
Net
Ref
Selected Data
00
0 1 Speed reference
10
Parameter write
data
11