Specifications

59
OBJECT MAP
7
[Input Instance 176 details]
*Bit status in the run command mode is as follows. (For the operation/speed command source, refer to page 30.)
Byte0
Bit0 Faulted
Inverter error signal
(0: inverter is under normal operation, 1: inverter is in a fault state)
Bit1
Run Command
Mode *
0: Command is disabled in network operation
1: Command is enabled in network operation
Bit2 Running Fwd Forward rotation (0: other than forward rotation, 1: forward rotation)
Bit3 Running Rev Reverse rotation (0: other than reverse rotation, 1: reverse rotation)
Bit4 Ready
Ready signal (0: operation preparation, 1: operation ready)
(Always "1" after power on)
Bit5 CtrlFromNet
State of operation command source (Run/Stop)
(Same definition with Class 0x29 Instance 1 Attribute 15
Refer to page 69
)
0: Command is enabled in operation other than network
1: Command is enabled in network operation
Bit6 RefFromNet
State of speed command source
(Same definition with Class 0x2A Instance 1 Attribute 29
Refer to page 71
)
0: Command is enabled in operation other than network
1: Command is enabled in network operation
Bit7 AtReference
Up-to-frequency signal (SU signal)
(Same definition with Class 0x2A Instance 1 Attribute 3
Refer to page 70
)
Byte1 Bit7 PrEnd
Parameter write is completed
0: Parameter write is not performed
1: During parameter write processing (during inverter processing)
(This bit may change to 1 during Explicit message processing.)
Byte2
Byte3
Speed Actual
Actual speed currently operating (r/min)
(Refer to page 42 for conversion formula of speed and frequency.)
Byte4
Byte5
Parameter
Read Data
Parameter write data specified by parameter class ID and parameter attribute ID of output
instance 126 is read. (Refer to page 57)
Inverter Status
Run Command Mode
Operation Mode Pr. 338 Pr. 339
NET
0: NET 0: NET 1
0: NET 1: External
0
1: External 0: NET
1: External 1: External
Other than NET ⎯⎯