Specifications

69
OBJECT MAP
7
*1 After reset with 01 set, this value must be set to 00 before inverter reset may be performed.
*2 This data is only updated after inverter reset or power-on reset.
*3 When this ID is set, it is reflected to bit7 to 11 of Pr. 346 and Class 0x05 Instance 2 Attribute 7, 13, 14 .
*4 When this ID is set, it is reflected to bit2 to 6 of Pr. 346 and Class 0x05 Instance 2 Attribute 8, 15, 16 .
(2) Service
9 Get Ready 1
0 During reset or alarm occurrence
1 Stop or running
10 Get Faulted 0
0 No fault present
1 Fault occurred (latched)
12 Get/Set
FaultRst
(fault reset)
*1
0
0 Reset release at fault occurrence
1 Reset execution at fault occurrence
15 Get
CtrlFromNet
(operation command
source monitor)
*2
1
0
Other than DeviceNet communication
operation
1 DeviceNet communication operation
140 Get/Set
Instance ID of Input
Assembly
*2, *3
0x47
(71)
0x46 Input Instance 70
0x47 Input Instance 71
0xB0 Input Instance 176
141 Get/Set
Instance ID of Output
Assembly
*2, *4
0x15
(21)
0x14 Output Instance 20
0x15 Output Instance 21
0x7E Output Instance 126
Service Code Description
0x0E Get Attribute Single
0x10 Set Attribute Single
Class 0x29 Instance 1
Attribute ID
Access
Name
Initial
Value
Range Description