Specifications

78
OBJECT MAP
Class 0x2A Instance 1
*1 Input terminal monitor details (when the terminal is ON: 1, when the terminal is OFF: 0, : undetermined value)
*2 Output terminal monitor details (when the terminal is ON: 1, when the terminal is OFF: 0,
: undetermined value)
(2) Service
b15 b0
⎯⎯⎯⎯⎯RES MRS RH RM RL ⎯⎯STR STF
b15 b0
⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯ABC FU ⎯⎯⎯RUN
Service Code Description
0x0E Get Attribute Single
0x10 Set Attribute Single
Attribute ID
Access
Description (Increments)
170 Get Output frequency (0.01Hz)
171 Get Output current (0.01A)
172 Get Output voltage (0.1V)
174 Get Frequency setting (0.01Hz)
176 Get Motor torque (0.1%)
177 Get
Converter output voltage
(0.1V)
178 Get
Regenerative brake duty
(0.1%)
179 Get
Electronic thermal relay
function load factor (0.1%)
180 Get
Output current peak
value(0.01A)
181 Get
Converter output voltage peak
value (0.1V)
183 Get Output voltage (0.01kW)
184 Get Input terminal status *1
185 Get Output terminal status *2
189 Get
Cumulative energization time
(1h)
192 Get Actual operation time (1h)
193 Get Motor load factor (0.1%)
194 Get Cumulative power (1kWh)
Attribute ID
Access
Description (Increments)