Specifications

87
OBJECT MAP
7
7.11 Class 0x80 (Extended Object IV)
7.11.1 Class 0x80 Instance 1
Inverter monitored value can be read. Refer to the Instruction Manual of the inverter for details of each
monitor.
(1) Attribute
*1 Input terminal monitor details
(when the terminal is ON: 1, when the terminal is OFF: 0, : undetermined value)
*2 Output terminal monitor details
(when the terminal is ON: 1, when the terminal is OFF: 0, : undetermined value)
Attribute
ID
Access
Description (Increments)
11 Get Output frequency (0.01Hz)
12 Get
Output current
(0.01A)
13 Get Output voltage (0.1V)
15 Get Frequency setting (0.01Hz)
17 Get Motor torque (0.1%)
18 Get Converter output voltage (0.1V)
19 Get Regenerative brake duty (0.1%)
20 Get
Electronic thermal relay function
load factor
(0.1%)
21 Get Output current peak value (0.01A)
22 Get
Converter output voltage peak
value
(0.1V)
24 Get Output power (0.01kW)
25 Get Input terminal status *1
26 Get Output terminal status *2
30 Get Cumulative energization time (1h)
33 Get Actual operation time (1h)
34 Get Motor load factor (0.1%)
35 Get Cumulative power (1kWh)
62 Get PID set point (0.1%)
63 Get PID measured value (0.1%)
64 Get PID deviation (0.1%)
71 Get Motor thermal load factor (0.1%)
72 Get Inverter thermal load factor (0.1%)
73 Get Cumulative power 2 (0.01kWh)
Attribute
ID
Access
Description (Increments)
b15 b0
⎯⎯⎯⎯⎯RES MRS RH RM RL ⎯⎯STR STF
b15 b0
⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯ABC FU ⎯⎯⎯RUN