6.8.15 PID manipulated variable gain (0.1Hz increments)
(network input config SNVT_freq_hz nciInvPIDOpeGain)
You can set the manipulated variable of the inverter in 0.1Hz increments when the deviation (difference
between set point and process variable) under PID control is 100%.
Data acceptance timing..... At network variable receive (nv_update_occurs event)
Data Name Initial Value Range Increments
Setting Value
Storage Location
nciInvPIDOpeGain Initial value of Pr. 125 (Pr. 903) 0.0Hz to 400.0Hz 0.1Hz/bit Pr.125(Pr.903)
REMARKS