Instruction manual

99
6
NETWORK VARIABLES
6.8.17 Maximum speed (0.005% increments) (network input config
SNVT_lev_percent nciMaxSpeed)
You can set the maximum speed to be output by the inverter to the motor.
Set the speed in 0.005% increments using the setting value of "reference speed setting (nciNmlSpeed)"
(Refer to page 100) or "reference frequency setting (nciNmlFreq)" (Refer to page 101) as reference.
Data acceptance timing........... At network variable receive (nv_update_occurs event)
6.8.18 Minimum speed (0.005% increments) (network input config
SNVT_lev_percent nciMinSpeed)
You can set the minimum speed to be output by the inverter to the motor.
Set the speed in 0.005% increments using the setting value of "reference speed setting (nciNmlSpeed)"
(Refer to page 100) or "reference frequency setting (nciNmlFreq)" (Refer to page 101) as reference.
Data acceptance timing........... At network variable receive (nv_update_occurs event)
Data Name Initial Value Range Increments
Setting Value
Storage Location
nciMaxSpeed Initial value of Pr. 1 0.000% to 163.830% 0.005%/bit Pr. 1/Pr. 18
REMARKS
Refer to the inverter manual for details of Pr. 1 or Pr. 18.
The setting value exceeding 163.830% is made invalid.
Control can not be exercised at less than the minimum frequency resolution (0.01Hz) of the inverter.
Data Name Initial Value Range Increments
Setting Value
Storage Location
nciMinSpeed Initial value of Pr. 2 0.000% to 163.830% 0.005%/bit Pr. 2
REMARKS
Refer to the inverter manual for details of Pr. 2.
The setting value exceeding 163.830% is made invalid.
Control can not be exercised at less than the minimum frequency resolution (0.01Hz) of the inverter.