100
NETWORK VARIABLES
6.8.19 Reference speed setting (network input config SNVT_rpm nciNmlSpeed)
Set the speed used as the reference of "speed adjustment (nviDrvSpeedScale)" (Refer to page 49), "speed
monitor (nvoDrvSpeed)" (Refer to page 50), "maximum speed (nciMaxSpeed)" (Refer to page 99) and
"minimum speed (nciMinSpeed)" (Refer to page 99).
* 1800r/min for the Japanese and NA version and 1500r/min for the EC and CH version.
Data acceptance timing........... At network variable receive (nv_update_occurs event)
The setting of reference speed setting (nciNmlSpeed) is changed from speed increments to frequency
increments, then written to Pr. 390.
Data Name Initial Value Range Increments
Setting Value
Storage Location
nciNmlSpeed 1800r/min / 1500r/min * 30r/min to 12000r/min 1r/min/bit Pr. 390
(the calculation result is rounded down.)
*
The number of motor poles is always four.
REMARKS
Refer to page 85 for details of Pr. 390.
Number of motor poles (4*) × speed
120
Frequency =