Instruction manual

103
6
NETWORK VARIABLES
z Network variables that allow setting of event driven detection width
Method for event driven detection... | Previous value - present value | event driven detection width
Name of Network Variables
In/
Out
100% Value
Formula of Detection Width
(0.005% increments)
Refer
to Page
Speed monitor (0.005%/bit)
SNVT_lev_percent nvoDrvSpeed
Out
As network variables supported and SNVT
of detection width are the same type, set the
value directly.
50
Output frequency monitor
(0.1Hz/bit)
SNVT_freq_hz nvoInvOutFreq
Out % set reference frequency 57
Output frequency monitor
(0.005%/bit)
SNVT_lev_percent nvoInvOutFreqP
Out
As network variables supported and SNVT
of detection width are the same type, set the
value directly.
58
Output current monitor (0.1A/bit)
SNVT_amp nvoDrvCurnt
Out Rated inverter current 59
Output voltage monitor (0.1V/bit)
SNVT_volt nvoDrvVolt
Out
Rated inverter voltage
(200V class: 200VAC,
400V class: 400VAC)
59
Cumulative power monitor 2
(0.1kWh/bit)
SNVT_elec_kwh_l nvoDrvRunPower_l
Out Rated inverter power × 2 61
Monitor data
SNVT_count nvoInvMonData
Out
The reference value of
100% differs according to
the monitor description.
(Refer to page 72)
75
Output frequency monitor (0.01Hz/bit)
SNVT_count nvoInvOutFreq2
Out % set reference frequency 76
Varying width of frequency
monitor value
× 100%
% setting reference frequency
Varying width of current
monitor value
× 100%
Rated inverter current
Varying width of voltage
monitor value
× 100%
Rated inverter voltage
Varying width of cumulative
power monitor value
× 100%
Rated inverter power × 2
Varying width of
monitor data value
× 100%
Reference value of
each monitor
V
ary
i
ng w
idth
o
f
f
requency
monitor value
× 100%
% setting reference frequency