Instruction manual

34
INVERTER SETTING
4.5 Inverter Reset
(1) Operation conditions of inverter reset
Which resetting method is allowed or not allowed in each operation mode is described below.
*1 Inverter reset can be made any time.
*2 Reset can be made only when the protective function of the inverter is activated.
Resetting Method
Operation Mode
Network
Operation
External
Operation
PU
Operation
Reset from the
network
Inverter reset (Command request network variable)
(Refer to page 77)
*1
Enabled Disabled Disabled
Error reset at inverter fault
(Inverter input signal network variable)
(Refer to page 61)
*2
Pr.349 = 0
Enabled
Enabled Enabled
Pr.349 = 1 Disabled Disabled
Turn on the inverter terminal RES (RES signal) Enabled Enabled Enabled
Switch off inverter power Enabled Enabled Enabled
Reset from the
PU/operation
panel
Inverter reset Enabled Enabled Enabled
Reset at inverter fault Enabled Enabled Enabled
CAUTION
When a communication line error has occurred, reset cannot be made from the network.
The inverter is set to the external operation mode if it has been reset in network operation mode in the initial
status.
To resume the network operation, the inverter must be switched to the network operation mode again.
Set a value other than "0" in Pr. 340 to start in network operation mode. (Refer to page 21.)
The inverter can not be controlled for about 1s after release of a reset command .