Instruction manual

41
6
NETWORK VARIABLES
6.2 Network Variable List
No.
Type
*4
Function
Network Variables
In/
Out
Setting Value
Storage
Location
Size
(byte)
Initial
Value
Refer
to
Page
Variables Name
1 SN Object request
SNVT_obj_request
nviRequest
In
3H046
2 SN Object status
SNVT_obj_status
nvoStatus
Out 6 H0 47
3SN
Start/stop and simple speed
setting
SNVT_switch nviDrvSpeedStpt
In 2
state=HFF
value=0
48
4 SN Speed adjustment
SNVT_lev_percent nviDrvSpeedScale
In 2 100.00% 49
5 SN Speed monitor
SNVT_lev_percent
nvoDrvSpeed
Out 2 0.000% 50
6 SN Inverter input signal
SNVT_state nviInvInputSig
In 2 0 51
7 SN Inverter output signal
SNVT_state nvoInvOutputSig
Out 2 H8000 53
8SN
Set frequency write destination
selection
SNVT_switch nviInvSetFreqSw
In 2
state=H0
value=0
55
9 SN Set frequency (0.1Hz/bit)
*1
SNVT_freq_hz nviInvSetFreq
In
RAM/
EEPROM of
the inverter
2H7FFF56
10 SN Set frequency (0.005%/bit)
SNVT_lev_percent
nviInvSetFreqP
In 2 100.00% 56
11 SN
Output frequency monitor
(0.1Hz/bit)
*1
SNVT_freq_hz nvoInvOutFreq
Out
20.0Hz57
12 SN
Output frequency monitor
(0.005%/bit)
SNVT_lev_percent
nvoInvOutFreqP
Out 2 0.000% 58
13 SN Output current monitor (0.1A/bit)
*1
SNVT_amp nvoDrvCurnt
Out 2 0.0A 59
14 SN Output voltage monitor (0.1V/bit)
*1
SNVT_volt nvoDrvVolt
Out 2 0.0V 59
15 SN
Actual operation time monitor (1 h/bit)
SNVT_time_hour
nvoDrvRunHours
Out
EEPROM of
the inverter
20h59
16 SN
Cumulative power monitor(1kWh/bit)
SNVT_elec_kwh
nvoDrvRunPower
Out 2 0kWh 60