Instruction manual

42
NETWORK VARIABLES
17 SN Alarm reset
SNVT_switch
nviInvAlarmReset
In
2
state=H0
value=H0
61
18 SN Alarm occurrence definition
SNVT_str_asc nvoInvAlarmStr
Out 31 0 62
19 SN
Product information (maker
name, type)
SNVT_str_asc nvoInvTypeInfo
Out
31
MITSUBISHI
FR-
A
7NL
64
20 SN Emergency stop command
SNVT_hvac_emerg nviEmergOverride
In 1 H0 65
21 SN Emergency stop status
SNVT_hvac_emerg
nvoEmergStatus
Out 1 H0 66
22 SN Alarm status
SNVT_switch nvoDrvAlarm
Out 2
state=H0
value=H0
67
23 SN PID set point (0.005%/bit)
SNVT_lev_percent
nviInvPIDTarget
In 2 0.000% 69
24 SN
PID measured value
(0.005%/bit)
SNVT_lev_percent
nviInvPIDValue
In 2 0.000% 70
25 SN PID deviation (0.005%/bit)
SNVT_lev_percent
nviInvPIDDev
In 2 0.000% 71
26 SN Monitor code
SNVT_count nviInvMonCode
In 2 0 72
27 SN Monitor data
SNVT_count nvoInvMonData
Out 2 0 75
28 SN Set frequency (0.01Hz/bit)
SNVT_count nviInvSetFreq2
In
RAM/
EEPROM of
the inverter
20.00Hz76
29 SN
Output frequency monitor
(0.01Hz/bit)
SNVT_count nvoInvOutFreq2
Out
20.00Hz76
30 SN Command request
SNVT_str_asc nviInvCmdReq
In 31 0 77
31 SN Command reply
SNVT_str_asc nvoInvCmdReply
Out 31 0 82
32 SC
Initial communication delay time
(0.1s/bit)
SNVT_time_sec nciPwUpOutTm
In Pr. 387 20s83
33 SC
Forward/reverse rotation
prevention
SNVT_count
nciInvFwdRevLock
In Pr. 78 2
*2
84
No.
Type
*4
Function
Network Variables
In/
Out
Setting Value
Storage
Location
Size
(byte)
Initial
Value
Refer
to
Page
Variables Name