Instruction manual

46
NETWORK VARIABLES
6.3.2 Object request (network input SNVT_obj_request nviRequest)
You can make a request to get the object status.
*1 Changes the invalid_request of the object status (nvoStatus) to "1" when data is set. (Refer to page 47)
*2 Use alarm reset (nviInvAlarmReset) to reset the alarm status of the inverter. (Refer to page 61)
*3 Can also be switched from switchover mode. (For details of switchover mode, refer to the inverter manual.)
Member Name Description
Initial
Value
object_id Stores the object ID.
H0
object_request
H0 RQ_NORMAL
In external operation mode *3, it shifts to the network
operation mode.
H1 RQ_DISABLED Makes the inverter object invalid.
H2 RQ_UPDATE_STATUS Update object status (nvoStatus).
H3 RQ_SELF_TEST Not supported.*1
H4 RQ_UPDATE_ALARM Updates in_alarm bit of the object status (nvoStatus).
H5 RQ_REPORT_MASK
Changes bit (invalid_id, invalid_request, disabled,
manual_control, in_alarm, in_override, report_mask)
supported by object status (nvoStatus) to "1".
H6 RQ_OVERRIDE Not supported.*1
H7 RQ_ENABLE Makes the inverter object valid.
H8 RQ_RMV_OVERRIDE Not supported.*1
H9 RQ_CLEAR_STATUS Clears all bits of the object status (nvoStatus) to "0".
HA RQ_CLEAR_ALARM Clears in_alarm bit of object status (nvoStatus) to "0".*2
HB RQ_ALARM_NOTIFY_ENABLED
Not supported.*1
HC RQ_ALARM_NOTIFY_DISABLED
HD RQ_MANUAL_CTRL Shifts the inverter to the external operation mode.
HE RQ_REMOTE_CTRL Shifts the inverter to the network operation mode.
HF RQ_PROGRAM Not supported.*1
HFF RQ_NUL Nothing is done.
Other than the above Not supported. *1