NETWORK VARIABLES
6.4 Variable Speed Motor Drive Object
6.4.1 Start/stop and simple speed setting (network input SNVT_switch
nviDrvSpeedStpt)
You can set "start/stop" and "simple setting of set frequency".
Set start/stop in state.
The rotation direction (forward/reverse rotation) is determined by whether "speed adjustment
(nviDrvSpeedScale)" (Refer to page 49) is positive or negative.
Set simple speed setting in value.
As the set frequency, set its ratio to "speed adjustment (nviDrvSpeedScale)" (0.5% increments).
* Operation of nviDrvSpeedStpt differs according to nviInvSetFreq. (Refer to page 56)
nviDrvSpeedStpt Operation *
State Value
nviInvSetFreq = "H7FFF" nviInvSetFreq = "0Hz to 400Hz"
H0 NA Stop
H1
0
(initial value)
Run at a 0% frequency.
0.5 to
100%
Run at a 0.5 to 100% frequency.
(nciNmlFreq × nviDrvSpeedStpt × nviDrvSpeedScale)
Run at an nviInvSetFreq frequency.
H2 to HFF
(initial value:
HFF)
NA No operation
REMARKS
The variable is initialized to "HFF" at power-on or if it is not updated at the "heartbeat receive time interval
(nciRcvHrtBt)" (Refer to page 97).
The inverter operates at value = 100% frequency even if "the value exceeding 100%" is set when state = "H1".
Updating nviDrvSpeedScale resets the start command depending on the state of nviDrvSpeedStpt.