NETWORK VARIABLES
6.5.7 Output frequency monitor (0.005% increments) (network output
SNVT_lev_percent nvoInvOutFreqP)
You can monitor the output frequency of the inverter in 0.005% increments on the assumption that the
frequency set in "% set reference frequency (nciInvSetFreqBas)" (Refer to page 85) is 100%.
Data send event ......................When data changes in 0.005% increments
Data send timing ..................... As set in Pr. 388 Send time interval at heart beat and Pr. 389 Minimum sending
time at heart beat. (Refer to page 87)
For example, when inverter output frequency = 90.0Hz and % set reference frequency = 60.0Hz,
Therefore, the monitoring value is 150.000%.
Data Name Initial Value Range Increments
nvoInvOutFreqP 0.000% 0.000% to 163.830% 0.005%/bit
REMARKS
Monitoring is disabled at less than the minimum frequency resolution (0.01Hz) of the inverter.
This variable is similar to "output frequency monitor (0.1Hz increments)" (Refer to page 57) but may sometimes differ
from it in data send timing since they are different in mutual resolution.
90.0Hz
60.0Hz
= 1.5