NETWORK VARIABLES
6.5.12 Cumulative power monitor 2 (0.1kWh increments)
(network output SNVT_elec_kwh_l nvoDrvRunPower_l)
You can monitor cumulative power of the inverter in 32 bit data and 0.1kWh increments.
Data send event ...................... At data change in 0.1kWh increments
Data send timing .....................Depends on the settings of Pr. 388 Send time interval at heart beat and Pr.
389 Minimum sending time at heart beat. (Refer to page 87)
6.5.13 Alarm reset (network input SNVT_switch nviInvAlarmReset)
You can reset the inverter at inverter alarm occurrence.
Data acceptance timing
......When network variables are being received and state = 1 (nv_update_occurs event)
Setting "1" in Pr.349 disables the alarm reset command in operations other than network operation.
Data Name Initial Value Range Increments
NvoDrvRunPower_l 0kWh 0 to 42949672.9kWh 0.1kWh/bit
REMARKS
If the value exceeds the maximum value of the monitor range, the value returns to 0 and is recounted from 0.
Data Name
Initial
Value
Range
Operation
state value
nviInvAlarmReset H0
H0
Don't care
(not used)
Without alarm reset
H1 Execute an alarm reset.
H2 to HFF Invalid
REMARKS
You can reset the inverter at inverter alarm occurrence. When the inverter is not during an alarm, performing this
operation does not reset the inverter.