Instruction manual

62
NETWORK VARIABLES
6.5.14 Alarm occurrence definition (network output SNVT_str_asc
nvoInvAlarmStr)
At inverter alarm occurrence, you can confirm the alarm definition of the inverter with a character string.
If an inverter alarm occurs at power-on/inverter reset, data is
not sent before the Pr.387 Initial communication delay time
(nciPwUpOutTm) (Refer to page 83).
The initial setting of +0 to +30 is 0.
Data send timing ......................At inverter alarm occurrence
Alarm Code Correspondence Table
Definition
+0 +1 +2 +3 +4 +5 +6 to +30
Alarm Code E . Character 1 Character 2 Character 3
OC1 H10
E(H45) .(H2E)
O(H4F) C(H43) 1(H31)
OC2 H11 O(H4F) C(H43) 2(H32)
OC3 H12 O(H4F) C(H43) 3(H33)
OV1 H20 O(H4F) V(H56) 1(H31)
OV2 H21 O(H4F) V(H56) 2(H32)
OV3 H22 O(H4F) V(H56) 3(H33)
THT H30 T(H54) H(H48) T(H54)
THM H31 T(H54) H(H48) M(H4D)
FIN H40 F(H46) I(H49) N(H4E)
ILF H52 I(H49) L(H4C) F(H46)
OLT H60 O(H4F) L(H4C) T(H54)
(Character 1)
(Alarm code)
(Character 2)
(Character 3)
(ASCII code)
+0
+2
+6 to +30
H
L
E
.
(H45)
(H2E)
(H00)
Storage position
+1
+3
+4
+5
Definition
Character 1
Character 2
Character 3